Laserfiche WebLink
ATTACHMENT E: ADDITIONAL COMMENTS <br /> 112.8(c)(6). CONTINUED - <br /> STI SP001 4TH EDITION IS NOT APPLICABLE TO TANKS HEATED ABOVE 200 DEGREES F: ALSO REQUIRES <br /> FORMAL EXTERNAL TESTING OF TANKS AT VARIOUS INTERVALS DEPENDING ON SIZE AND CATEGORY. <br /> TANK INPECTION/TESTING RECORDS INCLUDED AS PLAN APPENDIX G INDICATE THAT INSPECTOR WAS ONLY <br /> STI SP001 CERTIFIED, AND NOT QUALIFIED TO PERFORM INSPECTIONS OF THE LARGE FIELD-ERECTED <br /> TANKS. <br /> NO DETAILS PROVIDED ON TYPE AND SCHEDULE OF INSPECTIONITESTING FOR FIELD ERECTED TANKS IN <br /> ACCORDANCE WITH API 653. <br /> 112.8(c)(10) - STANDING OIL OBSERVED IN SECONDARY CONTAINMENT DURING INSPECTION . <br /> 112.8(c)(11) - PLAN STATES "NO REGULAR STORAGE OF PRODUCT IN MOBILE OR PORTABLE CONTAINERS IS <br /> CONDUCTED AT THE PACIFIC NORTHWEST OIL." OIL STORED IN DRUMS WAS OBSERVED AT THE FACILITY: <br /> AND DRUMS AND OTHER PORTABLE CONTAINERS ARE MENTIONED IN THE PLAN. <br /> Onshore Facilities (Excluding Oil Production) Page E-1 of 2 June 2014 <br />