up <br /> LINE LEAK DETECTOR TEST <br /> Facility #: 2186 Date: 02/22/11 <br /> Address: 3212 N. California <br /> City, State: Stockton, CA <br /> Testing Information <br /> 1 2 3 4 5 <br /> Product: 87 91 <br /> Manufacturer red jacket red jacket <br /> Leak Detector Serial Number n/a n/a <br /> Leak Detector Model No. cpt cpt <br /> Full Operating Pressure (psi): 31 31 <br /> Test Leak Rate (ml/min)(gph) 3.00 3.00 <br /> Bleed Back Rate (ml): 115 100 <br /> Turbine Holding Pressure (psi): 16 16 <br /> Metering Pressure (psi): n/a n/a <br /> Open/ Trip Time (mechanical only): n/a n/a <br /> Pass / Fail pass pass <br /> Comments: <br /> Note: Pass = Leak detector reads leak and meters line. <br /> Fail = Leak detector did not read leak. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment <br /> manufacturers procedures and limitations and the results as listed are to my knowledge true and correct. The mechanical leak test <br /> detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor FASTECH- Fueling & Services Technologies, Inc. <br /> Technician: Omar Ruiz Lic#: B35686 <br /> Signature: <br />