Line Leak Detector Test Data Sheet <br /> Station# Arco SS 2186 Date 1/13 2015 <br /> Address 3212 N. California <br /> Stockton, CA <br /> Test Information <br /> j 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure(psi) 31 psi 36 psi <br /> Line Bleed Back(ml) NA NA <br /> Trip Time(sec) NA NA <br /> Metering Pressure(psi) NA NA <br /> F/E Holding Pressure(psi) 19 psi 22 psi <br /> Test Leak Rate(ml/min)(gph) 189m 189ml <br /> PASS or FAIL P P <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Chris San Nicolas Lic# <br /> Signature <br />