Laserfiche WebLink
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 I 1 g <br /> Telephone: (209)468-3420 Fax: (209)468-3433 Web:www.si oq v org/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO 02186 3212 N CALIFORNIA ST, STOCKTON January 03, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item # Remarks <br /> 120 CCR 2635(d) Failed to submit UST Certification of Installation/Modification. <br /> A penetration fitting was replaced in UDC 5/6 under permit number SR0074967 in August 2016 and the UST <br /> Certification of Installation/Modification has not been submitted. This certification is required to be submitted within <br /> 30 days of completion of work to the California Environmental Reporting System(CERS). Immediately log into <br /> CERS, complete the required information, and submit for review by the EHD. <br /> This is a minor violation. <br /> 209 CCR 2715(c) Designated operator did not inspect all required items and/or the inspection reports not completed. <br /> The designated operator failed to visually inspect the 87 master fill sump for leaks, water, or debris during the May <br /> 2017 monthly inspection. The work order for the L6 (87 master fill sump)fuel alarm indicated that the liquid in the <br /> sump was removed by the facility and the technician did not open the sumps. During the monthly inspection, the <br /> designated operator shall visually inspect all spill containers and UDC sumps, and any tank top sump that had an <br /> alarm for which there is no record of a service visit and inspection by a qualified service technician. Ensure that <br /> designated operators performing monthly inspections at this facility are inspecting all of the required areas and <br /> noting it on the on the reports. <br /> This is a minor violation. <br /> 313 HSC 25290.1, 25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight. <br /> Fuel drips were noted on steel product piping under dispensers 1/2 and 7/8, indicating a leak in the primary piping. <br /> Moisture was observed on the floor of the UDC under the dripping piping in UDC 7/8. All primary containment for <br /> the UST system must be tight. Immediately have a properly licensed, trained, and certified contractor repair or <br /> replace the failed component under permit and inspection of the EHD. <br /> This is a minor violation. <br /> -- _.......... _- <br /> 315 HSC 25291(e)Water in secondary containment not removed, analyzed, and properly disposed of(pre-Jul 2003). <br /> Liquid was observed in UDC 1/2. If water could enter into the secondary containment by precipitation or infiltration, <br /> it must be removed and disposed of properly. The service technician removed approximately 1/2 gallon of liquid <br /> from UDC 1/2. Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a repeat violation, Class ll. <br /> Overall Inspection Comments: i <br /> This report has been amended on 1/4/18 to add violation #120. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by February 2, 2018. <br /> Please be aware that as of January 1, 2014, facility operators are required to upload the following UST program <br /> FA0006773 PR0231035 SCO01 01/03/2018 <br /> EHD 23-01 Rev.09/22/16 Page 4 of 5 Underground Storage Tank Program OIR <br />