Laserfiche WebLink
by <br /> 0 <br /> Line Leak Detector Test Data Sheet <br /> Station# Arco 2186 Date 1/3/2018 20 <br /> Address 3212 N. Califonia Stockton, CA 95204 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product <br /> 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure(psi) 29 31 <br /> Line Bleed Back(ml) NA NA <br /> Trip Time(sec) NA NA <br /> Metering Pressure(psi) NA NA <br /> F/E Holding Pressure(psi) 26 29 <br /> Test Leak Rate(ml/min)(gph) 18 9ML 18 9ML <br /> PASS or FAIL P p <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler Ryan Inc. <br /> Technician Alexander Tate Lic#220793 <br /> Signature <br />