Laserfiche WebLink
TANKNOLO6Y - UNDERGROUND LEAK DETECTION SYSTEM - (V3. 12) Page 19 <br /> CHEVRON Ck9 U-lVE349323-0612-O3 - Nov 02, 1993, 07:25 <br /> �1(4 LJ _F C-E"11:�: I- �EEIE3-I- E3 U M M ir4 Fe"al <br /> TEST DATE : Nov 02, 1993 <br /> START TIME : 07:25:23 <br /> CLIENT : CHEVRON <br /> LOCATION NAME : CHEVRON <br /> LOCATION CODE : 90302 <br /> TANK CONFIGURATION : Tandem <br /> TANK CONTENTS : RUN/RUN <br /> TANK NUMBER : Q:_" 04 <br /> TANK DIAME','ER : 94 94 in <br /> TANK CAPACITY : 12000 120)0 6 <br /> TANK MANUFACTURER : <br /> TANK MATERIAL : Steel Steel <br /> TANK REGISTRATION # : <br /> TANK DATE INSTALLED <br /> INITIAL DIPPED FUEL LEVEL : 78.00 79.00 in <br /> INITIAL DIPPED WATER LEVEL : 0.00 0.00 in <br /> POST PUMPING WATER LEVEL : 0 .00 0.00 in <br /> �%P.4 -IFF_="E3_V 9--.,r-- tJ L_-F <br /> TEST INITIAL WATER LEVEL : 0.00 0.00 in <br /> TEST FINAL WATER LEVEL : 0.00 0.00 in <br /> WATER INGRESS : 0 .00 0 .00 in � <br /> BUBBLE SIGNATURES : No No <br /> VACU-TECT TEST RESULT : Passed Passed <br /> ! <br /> COMMENTS: <br /> CONCLUSION: TANKS #3 & #4 TIGHT . <br /> ][ r4 rE �-kE!S3'-1- F.,�� &J L.--I- <br /> TEST RATE TEST RATE <br /> PREISJURE _OF 'LDSS_ PRESSURE <br /> #1 <br /> #2 <br /> #3 <br /> #4 <br /> #5 <br /> #6 <br /> COMMENTS: UNABLE TO PERFORM LINE TESTS DUE TO PUMP CONFIGURATION, <br /> NO LD PORT, NO VALVE TO ISOLATE LINE. <br /> CONCLUSION: <br /> This test was conducted in accordance with U.S. EPA Rule 40 CFR Parts 280 and 281. ' <br /> � � l ' ^ <br /> DAVID J. BAKE :ACU-TECT(tmV Test Number <br /> TANKNOLOGY ,- UNDERGROUND LEAK. DETECTION SYSTEM - (V3. 12) Pao�e 1 <br />