Laserfiche WebLink
-LUID DETECTION SYSTEM, FD103 <br /> The number of probes attached to one control center may <br /> be as many as 15. However the maximum number of probes <br /> is limited by the distance of the probes from the control and <br /> the current requirements of the probe. To determine the <br /> maximum number of probes that can be used for a specific <br /> installation configuration, refer to Figure 1.1. <br /> Figure 1.1 <br /> HIGH CURRENT PROBES LOW CURRENT PROBES <br /> FD221 V RA FD241 SRA FD221 T RA <br /> FD210RA FD241 GRA FD241 RRA <br /> FD210VRA FD221GRA FD241 PRA <br /> Distance to *Max.No. Distance to Max.No. <br /> Farthest Probe of Probes Farthest Probe of Probes <br /> 1000 Ft. 5 1000 Ft. 15 <br /> 500 Ft. 10 <br /> 200 Ft. 15 <br /> 100 Ft. 15 <br /> 'Each high current probe can be replaced by 5 low current <br /> probes. (Example: At 500 Ft. one of the (10) high current <br /> probes could be replaced by 5 low current probes for a new <br /> maximum condition of 9 high current probes and 5 low <br /> current probes). <br /> NOTE: THE MAXIMUM NUMBER OF PROBES THAT i <br /> CAN BE OPERATED FROM ANY ONE CONTROL <br /> CENTER IS LIMITED TO FIFTEEN (15). <br />