'EXHIBIT 5 <br /> Executive Order" G-70-52-AH <br /> Coaxial Hose Side-Mount High-Retractor Configuration <br /> For All New and Existing Installations <br /> Overhead Hose Retractor <br /> Retractor Swivel <br /> Coaxial Hose Assembly <br /> Nozzle <br /> 5 to 7 feet � <br /> Nozzle Swivel equal to or <br /> 9" maximum greater than 30° <br /> Gasoline Fluid Hose <br /> (or piping inside dispenser) <br /> Hose assembly sloped to permit <br /> natural drainage into vapor <br /> 22" minimum return piping when retractor is <br /> in retracted position. <br /> y Location of vapor check valve , <br /> if required. <br /> Riser (3/4 inch or Island Swivel (axisof swivel may <br /> larger inside diameter be rotated 90 from orientation <br /> galvanized pipe) shown) <br /> Note: 1 . See Exhibit 2 for the component list. <br /> 2. A flow limiter is required on dispensers that have a maxiamum flowrate in excess <br /> of 10 gpm. A flow limiter may be required on all gasoline dispensers at the <br /> option of the local air pollution control district. <br /> 3. A recirculation trap is not required. <br /> 4. Vapor return piping may be installed on the inside or on the outside of the <br /> dispenser cabinet. <br /> 5. The Emco Wheaton Model A4000 Series nozzles , and the OPW 11V Model F vapor <br /> recovery nozzles are permitted only when used in conjunction with approved <br /> vapor check valves. <br />