Laserfiche WebLink
INDIVIDUAL MMINE/LEAK DETECTOR TE; IEPORT <br /> TEST DATE: 08/18/97 TANKNOLOGY-NDEWORKORDER NUMBER: 2202260 <br /> CLIENT: ULTRAMAR INC SITE: ULTRAMAR #696 <br /> TANK INFORMATION <br /> Tank ID: 2 Material: DW STEEL Bottom to top fill in inches: 148.0 <br /> Product: PLUS Tank manifolded: NO Bottom to grade fill in inches: 153.0 <br /> Capacity in gallons: 9,728 Vent manifolded: NO Fill pipe length in inches: 56.0 <br /> Diameter in inches: 92.00 Vapor recovery manifolded: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 342 Impact Valves Operational: Y Stage I vapor recovery: DUAL <br /> Tank age (years): Overfill protection: Stage II vapor recovery: BALANCE <br /> Fuel pure rating: Overspill protection: YES Installed: ATG <br /> COMMENTS <br /> TANK TEST RESULTS „ Test Method: VPLT LEAK DETECTOR RESULTS Test method: <br /> PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced <br /> Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D. #2 <br /> UFT/OFT: Make: RED JACKET <br /> Fluid volume in gallons: Model: X.L.P. <br /> Tank water level in inches: S/N; 207947498 <br /> Test time: Open time in sec: 4.00 <br /> Number of thermisters: Holding psi: 16 <br /> Specific gravity: Resiliancy cc: 320 <br /> Water table depth in inches: Test leak rate ml/m: 189.0 <br /> Determined by (method): Metering psi: 10 <br /> Leak rate in gph: Calib. leak in gph: 3.00 <br /> Result: Results: PASS <br /> COMMENTS COMMENTS <br /> ULLAGE TEST RESULTSTest Method:UTS-4T LINE TEST RESULTS Test type: PTK-88 <br /> Test time: Material: DW FIBERG <br /> Ullage volume: Diameter(in): 2.0 <br /> Ullage pressure: Length (ft): 130.0 <br /> Results: Test psi: 50 <br /> Bleedback cc: 100 <br /> DATA FOR UTS-4T ONLY: Test time (min): 30 <br /> Test 1: Start time: 14:20 <br /> Time of test 1: Finish psi: 50 <br /> Temperature: Vol change cc: 0 <br /> Test 2: Start time: 14:30 <br /> Flow rate (cfh): Finish psi: 47 <br /> Time of test 2: Vol change cc: 12 <br /> Test 3: Start time: 14:40 <br /> Temperature: Finish psi: 50 <br /> Flow rate (cfh): Vol change cc: 0 <br /> Time of test 3: Final gph: 0.006 <br /> Temperature: Result: PASS <br /> Flow rate (cfh): Pump type: PRESSURE <br /> COMMENTS Pump make: RED JACKET <br /> COMMENTS <br /> Draft 08/26/97 15:13 MSHAW <br /> 8900 SHOAL CREEK, BUILDING 200,AUSTIN,TEXAS 78757(512)451-6334 <br />