Laserfiche WebLink
JUN-26-2008 17: 17 Service Station Systems 408 938 8888 P.04 <br /> Monitoring System Certification-Pa, of 3 <br /> Site Address: 2448 W. Kettleman Ln. @ Lower Sacramento Date of Testing/Servicing: 5128108 <br /> D. Results of Testing/Servicing <br /> Software Version Installed• 122.0 <br /> Com tete the foliowin checklist: <br /> *Yes ❑ No* Is the audible alarm operational? <br /> *Yes ❑ No* Is the visual alarm operational? <br /> 13'Yes Cl No* Were all sensors visually inspected, functionally tested, and confirmed operational? <br /> tg Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relaved to a remote monitoring station, is all communications equipment(e.g. modem) <br /> Z N/A operational? <br /> CK Yes ❑ Nos For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate; <br /> positive shut-down? (Check all that apply) 2 Sump/Trench Sensors; ❑ Dispenser Containment Sensors. <br /> Did you confinn positive shut-down due to leaks and sensor failure/discorurection? CK Yes ❑ No <br /> tx Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank-overfill warning device(i.e. no <br /> ❑ N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fillpoint(s)and operating properly? If so, at what percent of tank capacity does the alarm trigger? 90 % <br /> ix Yes' ❑ No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E, below_ <br /> ❑ Yes* a No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑ Product:❑ Water. If yes,describe causes in Section E,below. <br /> la Yes ❑ Nos Was monitoring system set-up reviewed to ensure proper settings? (Attach set-up reports, if applicable.) <br /> Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications? <br /> * In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: Replaced leak detector on 91 turbine <br />