ELECTRICAL SPECIFICATIONS <br />GENERAL NOTES: <br />1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA <br />CODE OF REGULATIONS, INCLUDING THE FOLLOWING: <br />TITLE 24, CCR, PART 2, 2016 CBC <br />TITLE 24, CCR, PART 3, 2016 CEC <br />TITLE 24, CCR, PART 4, 2016 CMC <br />TITLE 24, CCR, PART 9, 2016 CFC <br />ALL APPLICABLE LOCAL CODES. <br /> <br />2. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, ETC. <br />REQUIRED TO CARRY ON AND COMPLETE THE WORK. PERMIT BY OWNER. <br /> <br />3. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND <br />PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER <br />EXECUTION AND COMPLETION OF ALL "ELECTRICAL WORK" WHETHER SPECIFICALLY <br />MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED HEREIN, AND/OR IMPLIED THEREBY TO <br />CARRY OUT THE APPARENT INTENT THEREOF. <br /> <br />4. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' <br />LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL <br />WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY <br />FURNISHED BY THAT AGENCY. <br /> <br />5. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE <br />AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, <br />CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND VERIFY <br />THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT <br />AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. <br /> <br />6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESS OTHERWISE <br />NOTED OR REQUIRED BY CODE. <br /> <br />7. ALL LUMINAIRES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER TO THE <br />CALIFORNIA ENERGY COMMISSION. <br /> <br />8. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND <br />SWITCHES BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST. <br /> <br />9. ALL EXIT SIGNS TO BE UNSWITCHED. <br /> <br />NAMEPLATES & IDENTIFICATION: <br /> <br />INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC. <br />NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS <br />ROUND HEAD CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT, OR WITH A PLASTIC <br />RESIN ADHESIVE GLUE, GOODYEAR "PLIEBOND" OR EQUAL. <br />HVAC UNIT DISCONNECTS: <br /> <br />1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR <br />EXACT LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. VERIFY AND <br />CONFIRM THE ACTUAL MOUNTING LOCATION ON THE HVAC UNIT FOR THE DISCONNECT. <br /> <br />2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST FUSE <br />SIZE ON THE UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE FUSES OF <br />THIS RATING. <br /> <br />3. FURNISH AND INSTALL ALL LINE VOLTAGE AND LOW VOLTAGE CONDUITS AND LINE <br />VOLTAGE WIRING (LOW VOLTAGE WIRING BY OTHERS) TO HVAC EQUIPMENT AND <br />ASSOCIATED CONTROLS AND DEVICES AS SHOWN ON THE ELECTRICAL AND MECHANICAL <br />PLANS, UNLESS OTHERWISE NOTED. <br />WIRING METHODS: <br /> <br />1. ALL WIRING SHALL BE INSTALLED IN STEEL CONDUITS, CONCEALED IN WALL AND <br />CEILING U.O.N. <br /> <br />2. MINIMUM CONDUIT SIZE SHALL BE 1/2". MINIMUM ACCEPTABLE CONDUITS ARE <br /> A. GALVANIZED RIGID STEEL. <br /> B. GALVANIZED STEEL EMT. <br /> C. LIQUID TIGHT STEEL FLEX -FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. <br /> D. FLEXIBLE STEEL CONDUIT -FOR INDOOR FINAL CONNECTIONS TO <br /> MECHANICAL EQUIPMENT (NOT TO EXCEED 36"). <br /> E. PVC CONDUIT SCHEDULE 40, UNDERGROUND. <br />3. NMC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING. <br />4. MC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING. <br /> <br />WIRING DEVICES: <br /> <br />UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS <br />(BROWN, WHITE, GREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT: <br /> A. WIRING DEVICES LEVITON # HUBBELL # P & S # <br /> SINGLE POLE SWITCH 1221 1221 20AC1 <br /> THREE WAY SWITCH 1223 1223 20AC3 <br /> DUPLEX CONV. OUT. 15A 5262 5262 5262 <br /> DUPLEX GFI CONV. OUT. GF5262 <br />DEVICE PLATES: <br />1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE SMOOTH NYLON OR APPROVED EQUAL <br />UNLESS OTHERWISE NOTED. ALL DEVICE PLATES FOR OUTDOOR USE SHALL BE RAISED <br />METAL. <br />2. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES. <br />WEATHERPROOF COVERS TO BE SNAP TYPE COVERS. <br />3. DEVICE PLATES FOR TELEPHONE AND COMPUTER OUTLETS TO BE PROVIDED BY <br />OWNER'S VENDOR. ALL TELEPHONE AND COMPUTER SYSTEM WIRING BY OWNER'S <br />VENDOR. <br />SUPPORTS: <br /> <br />1. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL <br />ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT. <br /> <br />2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO <br />METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS <br />AND MACHINE SCREWS OR BOLTS. <br />GROUNDING: <br /> <br />1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND <br />SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC. <br />WORKING CLEARANCES FOR PANELS & SWITCHBOARDS <br /> <br />1. COORDINATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING <br />CLEARANCES, ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.E.C. SECTIONS <br />110-16 AND 384-4. <br />TESTING: <br />1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS AND <br />IMPROPER GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND <br />GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND WHETHER SUCH <br />TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY SHALL BE LOCATED, <br />REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE. <br />2. DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE INSTALLATION <br />IS COMPLETE, IN PROPER OPERATING CONDITION AND THAT THE CONTRACT HAS BEEN <br />PROPERLY AND FULLY EXECUTED. PROVIDE ALL INSTRUMENTS TO MAKE SUCH TESTS. <br />TYP1 <br />TRACK LIGHTING WITH SUSPENSION <br />ROAD, TRACK, HEADS AND ALL <br />ACCESSORIES <br />B (b)B (b)B (b)B (b)B (a)B (a)B (a) <br />B (a)B (a) <br />B (a)B (a) <br />B (d) B (d) B (d)B (c)B (c) <br />B (c) <br />B (c) <br />B (c) <br />A (e) <br />A (e) <br />A (e)A (e) <br />A (h) <br />A (h)A (h) <br />A <br />C (f) <br />C (f) <br />C (f)C (f)C (f) <br />D (g) <br />PDT <br />PDT <br />PDT <br />PDT PDT <br />PDT <br />51 <br />52 <br />DRC <br />DRC <br />DRC <br />DRC <br />DRC <br />DRC <br />DRC <br />DRC <br />PE <br />TIE PHOTOCELL INTO DIMMING <br />CONTROLS FOR ZONES b & dDIMMING ZONE CONTROLLER <br />TO SUIT LIGHTS PROVIDED <br />BY CONTRACTOR AND <br />OWNER <br />US US <br />US US <br />US <br />PROVIDE MOTION SENSORS <br />AND INTERTIE SO THAT ANY <br />OCCUPANY SENSOR MAINTAINS <br />ALL LIGHTING ZONES <br />DINING <br />101 <br />BAR SEATING <br />102 <br />BAR <br />103 <br />KITCHEN <br />104 <br />DISH WASHING <br />105 <br />RR <br />107 <br />C (f)C (f)C (f) <br />TO DRC-a <br />PANEL K <br />K-22 <br />K-22 <br />K-22 <br />A <br />K-24 <br />K-24 <br />0-10V DIMMING <br />LIGHT FIXTURES <br />- OR - <br />LINE VOLTAGE DIMMING <br />WALL MOUNT <br />SWITCH WITH <br />ON/OFF POWER <br />AND RAISE <br />LOWER <br />CONTROL <br />DIMMING ROOM <br />CONTROLLER <br />WITH CAT5 INPUTS FOR <br />LIGHT SWITCHES, <br />MOTION SENSORS, <br />DAY LIGHT PHOTOCELL <br />CEILING <br />OCCUPANCY <br />SENSOR <br />CEILING <br />PHOTOELECTRIC <br />SENSOR <br />LINE VOLTAGE <br />INPUT <br />LINE VOLTAGE <br />CONTROL & <br />DIMMER <br />CONTROL <br />TO <br />SECOND <br />TO <br />SECOND