Laserfiche WebLink
SAN J O A Q U I N Environmental Health Department <br /> COUNTY- <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> NORCAL TRANSPORT REFRIGERATION 3730 E MUNFORD AVE, STOCKTON May 09, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 718 CFR 112.8(c)(11) Failed to locate properly or provide sufficient secondary containment for mobile/portable <br /> containers. <br /> Two 55 gallon drums of motor oil were observed with insufficient secondary containment. One blue metal and one <br /> red metal drum of motor oil were observed on the north wall of the shop without secondary containment. Portable oil <br /> storage containers must be positioned or located to prevent a discharge and shall be furnished with a secondary <br /> means of containment sufficient to contain the capacity of the largest single container with sufficient freeboard to <br /> contain precipitation. Immediately provide sufficient secondary containment for this and all other portable containers <br /> at this facility, or provide equivalence as allowed by CFR 112.7(a)(2). <br /> On page 8 of the SPCC plan the plan states that there will be oil drums on site. On page 9 of the SPCC Plan on the <br /> facility map one oil drum is indicated. On page 31 of the SPCC plan it says that the facility"has no mobile or <br /> portable containers within their oil product system". Two 55 gallon drums of motor oil were observed during the <br /> inspection. For mobile or portable containers,either provide the type of oil and storage capacity for each container <br /> or provide an estimate of the potential number of mobile or portable containers,the types of oil, and anticipated <br /> storage capacities. Ensure that the SPCC plan accurately reflects portable and mobile containers. Submit a copy of <br /> the amended plan to the EHD for review. <br /> This is a Class II violation. <br /> 720 CFR 112.8(d)(1) Failed to provide corrosion protection for buried piping. <br /> -The facility map on page 9 of the SPCC plan indicates buried piping from the 12,000 gallon diesel tank to the fuel <br /> island. Page 30 of the SPCC plan states that"there is no underground piping on site for the oil products". <br /> Buried piping that is installed or replaced after August 16, 2002,shall be provided with a protective wrapping and <br /> coating and cathodically protected. Immediately provide all buried piping installed on or after August 16, 2002, a <br /> protective wrapping and coating and cathodic protection and ensure that the SPCC plan accurately discusses the <br /> buried piping in the SPCC plan. Submit a copy of the amended SPCC plan to the EHD. <br /> This is a Class II violation. <br /> 4010 The Substantial Harm Criteria certification form was not included with the SPCC plan. If the facility does not meet <br /> the substantial harm criteria listed in Attachment C-1 to this appendix,the owner or operator shall complete and <br /> maintain at the facility the certification form contained in Attachment C-II to this appendix. In the event an alternative <br /> formula that is comparable to the one in this appendix is used to evaluate the substantial harm criteria,the owner or <br /> operator shall attach documentation to the certification form that demonstrates the reliability and analytical <br /> soundness of the comparable formula and shall notify the Regional Administrator in writing that an alternative formula <br /> was used. Ensure that the SPCC plan contains the Substantial Harm Criteria certification form. Submit a copy to <br /> the EHD. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> FA0014437 PR0531150 SCO02 05/09/2019 <br /> EHD 28-01 Rev.09/27/2018 Page 5 of 6 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />