Laserfiche WebLink
Position-Sensitive Sensor installation Manual Sensor Setup Notes <br /> SENSOR WIRING <br /> 1. Screw the connector on the end of the sensor cable onto the plug in the top of the sensor housing. <br /> 2. Install the Cord Grip supplied with the wiring kit in the pan/sump junction box in which the field wiring from the <br /> console terminates. <br /> 3. Coil up the excess cable and tie wrap it out of the way.Feed the two-lead end of the sensor cable through the cord <br /> grip in the junction box.Tighten the cord grip nut to ensure a watertight seal at the cable entry. <br /> 4. Using wire nuts,connect the two-wire cable to the field wires from the console as shown in Figure 4. <br /> i Black <br /> To i i • <br /> Interstitial i <br /> Sensor i Seal-off i i From <br /> Interface i i Sensor <br /> Module i i ® White <br /> i "'11/2"rigid <br /> conduit <br /> Epoxy sealed connections in a <br /> sensors\ddpswir.eps weatherproof junction box <br /> Figure 4. Sensor Wiring Connections(No Polarity) <br /> 5. Seal wire nuts with epoxy sealant following the instructions in Figure 5. <br /> b a <br /> CAUTION:Epoxy sealant is irritating to eyes,respiratory system, and skin.Can cause allergic skin reaction.Con- <br /> tains:epoxy resin and Cycloaliphatic epoxycarboxylate.Precautions:Wear suitable protective clothing,gloves,eye, <br /> and face protection.Use only in well ventilated areas.Wash thoroughly before eating,drinking,or smoking. <br /> 6. Push the epoxy sealed bag into the junction box Replace and tighten the junction box cover. <br /> Sensor Setup Notes <br /> Setting up the console to monitor Position-Sensitive Sensors is done under the Liquid Sensor setup function.For the <br /> LIQUID SENSOR TYPE entry,select TRI-STATE(SINGLE FLOAT).Make additional sensor setup selections as <br /> required. <br /> 5 <br />