Laserfiche WebLink
f <br /> Hazardous Waste Tank System July <br /> Written Assessment per CCR Title 22 <br /> i <br /> Tracy Toyota, 2895 Naglee Road,Tracy,CA 905304 2014 <br /> i <br /> 3 <br /> Seismic Calculation <br /> Waste Antifreeze Tank 2 <br /> Cylindrical, Vertical Closed Top, Flat Bottom, Sin le Walled <br /> Material of Construction: HDPE <br /> Shell Height, in 49.00 <br /> Shell Diameter, in 36.00 <br /> Working Volume, gal 194.00 <br /> S.G. of contents 1.05 <br /> Tank Wall Thickness, in 0.31 <br /> Total Weight of Tank and Contents, Ibs 1863.00 <br /> Overturninq Moment Arm in 22.00 <br /> Resisting Moment Arm, in 18.00 <br /> Sds 1.04 <br /> Importance Factor 1.00 <br /> Fp, ASCE 7-10, 15.4-2 581.26 <br /> Overturning Moment inlbf 12787.63 <br /> Resisting Moment inlbf 33534.00 <br /> Overturning Safety Factor- No Tension 2,62 <br /> Shear Strength of Anchor. Lbs 1680.00 <br /> # of Anchors 1.00 <br /> Factor of Safety for Shear 2.89 <br /> Seismic/Anchoring findings: The tank as designed and operated and the <br /> containment area in which it is located are equately anchored and are <br /> i <br /> seismically sound. Initials: <br /> Strandberg Associates 1(866) 388-0404 rwaterquuy(c�rwater u .conn 21 <br /> i <br /> d <br /> 3 <br /> t <br />