Laserfiche WebLink
Hazardous Waste Tank System July <br /> Written Assessment per CCR Title 22 <br /> Tracy Toyota, 2895 Naglee Road,Tracy, CA 905304 2014 J! <br /> Seismic Calculation <br /> I <br /> i <br /> Seismic Calculation -Waste Oil Tank 2 <br /> Rectangular, Vertical Closed Top, Flat Bottom Double Walled <br /> Material of Construction: steel l <br /> Shell Height, in 96.00 <br /> Shell Length, in 39.00 ? <br /> Working Volume, gal 540.00 I <br /> S.G. of contents 0.95 ! <br /> Tank Wall Thickness, in 0.14 <br /> Total Weight of Tank and Contents, lbs 6230.00 <br /> Overturning Moment Arm, in 48.00 <br /> Resisting Moment Arm, in 19.50 <br /> Sds 1.04 <br /> Importance Factor 1.00 <br /> Fp, ASCE 7-10, 15.4-2 1943.76 <br /> Overturning Moment inlbf 93300.48 <br /> Resisting Moment, inlbf 121485.00 <br /> Overturning Safety Factor- No Tension 1.30 <br /> Shear Strength of Anchor. Lbs 723.00 <br /> #of Anchors 3.00 <br /> Factor of Safety for Shear 1.12 <br /> Seismic/Anchoring findings: The tank afuately <br /> igned and operated and the <br /> containment area in which it is located are anchored and are <br /> seismically sound. Initials: <br /> i <br /> Tank Integrity: Tank age: Estimated 9 years <br /> Strandberg Associates 1(866) 383-0404 rwater a rwaterquy coin 32 <br /> i <br />