Laserfiche WebLink
SA NA MU I N Environmental Health Department <br /> COUNTY— <br /> Aboveground Petroleum Storage Act Inspection Report <br /> FacilityNa e: I Facility Address: nata- <br /> MARTIN-BROWER CO 4704 FITE CT,STOCKTON April 30, 2019 <br /> SUMMARY OF VIOLATIONS <br /> IU ASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item M Remarks <br /> 706 CFR 112.8(cx2)Failed to provide and maintain adequate secondary containment. <br /> The two 500 gallon new oil single walled tanks were observed with insufficient secondary containment. The SPCC plan <br /> describes the two tanks as being within a low curbed area and secondary containment calculations describe the bermed <br /> area as being able to contain 500 gallons.The two 500 gallon new oil tanks were not observed within a curbed or <br /> bermed area.The two 500 gallon tanks did not appear to have secondary containment.Construct all bulk storage tank <br /> installations(except mobile refuelers and other non-transportation-related tank trucks)so that you provide a secondary <br /> means of containment for the entire capacity of the largest single container and sufficient freeboard to contain <br /> precipitation.You must ensure that diked areas are sufficiently impervious to contain discharged oil. Dikes,containment <br /> curbs,and pits are commonly employed for this purpose.You may also use an alternative system consisting of a <br /> drainage trench enclosure that must be arranged so that any discharge will terminate and be safely confined in a facility <br /> catchment basin or holding pond.. Immediately provide sufficient secondary containment for this and all other tanks at <br /> this facility. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by May 30, 2019 . <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate($152). To schedule an <br /> appointment, please call (209)468-3420. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING THIS <br /> FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EH D'S CURRENT HOURLY RATE. <br /> R-craiv-d by: Det-: Apri130,2019 bepector: heiRector Peon.: <br /> PaaAd <br /> N.And <br /> rR-: CESAR RUVALCABA,REHS (209)953-6213 <br /> Casey Hays, Dishibution Process Manager <br /> FM01i693 PRO5 3W SC301 0M300019 <br /> EHDM8 I Rer.0.l9/A1S Page 5of5 Aiaaveg J Perdeum Stara)e AC OIR <br /> 1868 E. Hazelton Avenue I Stockton,California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />