Owens-Brockway Spill Prevention,Control,and Countermeasure Plan <br /> Plant#22 <br /> Table 2.4 <br /> Secondary Containment Volume Calculations <br /> Plant#22 <br /> Tracy,California <br /> Displaced Volumes <br /> Secondary Containment Area (1)100 gal Fuel Tank <br /> (Gen-A) Displacement Description Diameter(ft) Length Width Height(ft) Displaced Height(height below Quantity Displaced Volume <br /> (ft) (ft) containment wall)(ft) (gals) <br /> Containment Type(Angle Irons on Concrete) Steel Base of Fuel Tank 0.00 0.00 0.00 0.0 1 0 <br /> Length(ft) 5.0 Note:The fuel tank will empty no lower than the height of the secondary containment.Therefore there is no displacement volume. <br /> Top Width(ft) 9.1 <br /> Height(ft) 0.3 <br /> Containment Volume(gals) <br /> Largest Tank-(1)100 gal Fuel Tank <br /> Length(ft) NA <br /> Width(ft) NA <br /> Height(ft) NA <br /> Quantity 1 <br /> Largest Tank Shell Volume(gals) 100 <br /> Calculation Summary <br /> Containment Volume(gals) 114 <br /> Largest Tank Shell Volume(gals) 100 <br /> Total Displaced Volume(gals) 0 <br /> Excess/Deficiency for 110%release(gals) 4 <br /> G-1189091 u)APPs CHID Services,Inc. <br />