Laserfiche WebLink
SAN <br /> FOA U I N Environmental Health Department <br /> b :.3UsNTY--.._ <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: pate; <br /> INTERSTATE TRUCK CNTR 2110 S Sinclair Ave,Stockton May 29,2019 <br /> Other Violations <br /> 4030 See below Unlisted❑peratio nslMaintenance violation ❑V r,R ❑COS <br /> 4040 See below Unlisted ReIeaselLeakS/Spills violation o V QR ❑COS <br /> 4050 See below Unlisted AbandonmenV1Ileg al I7lsposallUnauthorized Treatment violation V R r,COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS It,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 341 CFR 112.5(x)Failed to amend Plan as necessary. <br /> One approximately 100 gallon{portable diesel tank was observed in the service area and is not included in the SPCC <br /> plan. One green double wall temporary motor ail tank was observed in the body shop and is not included in the <br /> SPCC plan. One approximately 125 gallon temporary portable diesel tank was observed In the body shop and was <br /> not included In the SPCC plan. The Spill Prevention,Control, and Countermeasure(SPCC)Plan must be amended <br /> when there is a change in the facility design, construction, operation, or maintenance that materially affects its <br /> potential for a discharge,within 6 months of the change,and implemented as soon as possible, not later than 6 <br /> months following preparation of the amendment. Immediately make all necessary amendments to the SPCC Plan to <br /> accurately represent the procedures and policies currently in place at the facility and submit a copy to the EHD_ <br /> This is a minor violation. <br /> fit CFR 112.7(e), I12.8(c)(6)Failed to keep records of procedures, inspections,or integrity tests for three years. <br /> -Copies of annual inspections for the 9000 gallon used oil tank,the 500 gallon oil tank,the 375 gallon oil tants,the <br /> 240 gallon transmission oil tank,and the 240 gallon gear ail tank were not found on site. <br /> -2019 monthly inspection logs were not signed by the inspector or supervisor. This was corrected on site. <br /> Inspections and tests must be conducted in accordance with the written procedures developed in the Spill <br /> Prevention,Control, and Countermeasure(SPCC)Plan. Records of these inspections and tests must be signed by <br /> the appropriate supervisor or inspector and kept on site with the SPCC Plan for a period of three years. <br /> Immediately locate a copy of all inspection and testing records for the last three years, maintain them on site, and <br /> submit copies to the EHt7. <br /> This is a repeat violation,Class II. <br /> 61 CFR 112.7(f)(1)Failed to train personnel on all discharge prevention details listed in this section. <br /> Oil handling person net training was not documented. SPCC plan site specific training was not documented for RJ <br /> Beckham(Hazardous Waste Coordinator)and JR. Page 20 of the SPCC plan states that training records will be <br /> kept for a minimum of three years. At a minimum, oil handling personnel shall be trained in the operation and <br /> maintenance of equipment to prevent discharges; discharge procedure protocols; applicable pollution control laws, <br /> rules, and regulations;general facility operations; and the contents of the Spill Prevention,Control, and <br /> Countermeasure Plan. Immediately provide this training to all oil handling personnel and submit a copy of the training <br /> lag to the EHD_ <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> FAOD23082 PRO540743 SCO01 05!2912079 <br /> EHp 28-01 Rev.09/27/201 S Page 4 of 5 Abovegro d Petroleum Storage Act OR <br /> 1868 E. Hazelton Avenue 1 Stockton, California 95205 1 T 209 458-3420 1 F 209 464-0138 1 www.sjcehd.com <br />