Laserfiche WebLink
210 East Wetmore Street PR0544025 <br /> June 26, 2019 Program: APSA <br /> PHOTO 5: Inspection/testing schedule deviates from SP001 standard discussed in SPCC plan. No environmental equivalence provided. <br /> TABLE:8 <br /> Scope and Frequency of AST Container Inspections and Tests <br /> CITY OF MANTECA VEHICLE MAINTEIVANCE AND CORPORATE YARD <br /> 205/210 Wetmore Street/410 S.Main Street,Manteca,California <br /> [E ---Inspection/Test Tank IDDiesel Wa,ite Oil Motor Oil Drums <br /> l Inspection by Facility personneler checklist of Appendix C) M,A MI,A M,A M,A <br /> nal inspetion by certified inspector <br /> r STI Standard SP-0011 20 yr 20 yr 10 yr <br /> al inspection by certifiedinpector <br /> r STI Standard SP-001 t t 20 yr*Ig Hess es. mee Ing requlremen sFR 280 2 yr <br /> The frequency above is based on implementation of a scheduled inspection/testing program.To initiate the program,ASTs will be inspected by the <br /> following dates: <br /> C ASTImplementation of Testing Date <br /> Diesel Fuel AST Following shell repairs or as directed by local <br /> Waste Oil AST Following shell repairs or as directed by local <br /> Bulk Oil AST Following shell repairs or as directedby local <br /> Notes <br /> AST:aboveground storage tank <br /> STISteel Tank Institute <br /> SP 001:standard and number designation <br /> M:Monthly <br /> A:Annual <br /> Or earlier,as recommended by the certified inspector based on findings from an external inspection. <br /> t Internal inspection may be recommended by the certified inspector based on findings from the external inspection. <br /> CFR,code of federal regulations <br /> Advmrced CaEnvimmmiat,llna <br /> Lydia Baker, REHS Page 5 of 5 <br />