Laserfiche WebLink
SAN JOAQUIN COUNTY <br />ENVIRONMENTAL HEALTH DEPARTMENT <br />600 East Main Street, Stockton, California 95202-3029 <br />Telephone: (209) 468-3420 Fax: (209) 468-3433 Web: www.sigov.org/ehd/unitiii.html <br />CONTINUATION FORM <br />Page: 3 of 5 <br />OFFICIAL INSPECTION REPORT <br />Date: 01/26/11 <br />Facility Address: Cherokee Lane Service Station 900 Cherokee Ln Lodi, CA 95240 <br />Program: UST <br />SUMMARY OF VIOLATIONS <br />CLASS I, CLASS II, or MINOR -Notice to Comply) <br />On site to witness the annual monitoring system certification testing and perform the routine inspection. <br />#3 UST tank forms on file with the EHD are not current. Any change of information on these forms must <br />be submitted to the EHD within 30 days of the changes. Immediately complete and submit a copy of the <br />facility and tank forms to the EHD. Complete a separate tank form for each tank. <br />#4 Financial responsibility documents have not been submitted to the EHD. Current financial <br />responsibility documents are required to be submitted annually. Complete and submit a copy of the <br />financial responsibility immediately. <br />#5 & 6 Current approved copies of the monitoring and response plans were not found on site. The <br />monitoring and response plans must be current and approved by the EHD. Complete and submit a copy <br />of the response plan for approval by the EHD by 11-27-10. An approved copy will be returned for your <br />records. <br />#11 The 87A (west) stp and diesel stp sump sensor were approximately 3 inches higher than the lowest <br />point of the sump almost and not properly located to detect a leak at the earliest opportunity. The 91 stp <br />sump sensor was laying on its side and not properly located to detect a leak at the earliest opportunity. <br />Monitoring equipment shall be maintained to be able to detect a leak at the earliest possible opportunity. <br />Technician corrected this during the inspection by repositioning the sensor to the lowest part of the stp <br />sump. <br />#21 Liquid was observed in the south diesel satellite udc. If water could enter into the secondary <br />containment by precipitation or infiltration, it must be removed and disposed of properly. Technician <br />removed this liquid and placed into the hazardous waste drum on site. Ensure that the dispenser udc's <br />and tank sumps are maintained free of liquid. <br />#23(c) On the November 2010 designated operator report, the designated operator failed to check and <br />note the correct test dates for annual monitoring system certification testing. The annual monitoring <br />system certification test date was documented as 10-27-10 but should have been documented as <br />10-6-09. During the monthly inspection, the designated operator shall check that all required testing and <br />maintenance for the UST system have been completed and document the dates they were done. <br />Ensure that designated operators performing monthly inspections at this facility are including all of the <br />required information on the reports. <br />ALL EHD STAFF TIME ASSOCIATED WITH FAILING TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE CURRENT HOURLY RATE ($122). <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br />EHD Inspector b� <br />Received By: <br />Title: <br />EHD 23-02-003 Rev 68110!10 CONTINUATION FORM <br />