Laserfiche WebLink
ITTSIntegrity Tank Testing Systems, Inc. <br /> October 17 , 1990 <br /> Mr. Len Bohlke <br /> VILLAGE WEST MARINA <br /> 6649 Embarcadero JUN 2 4 1991 <br /> Stockton, California 95209 ENVIRONMENTAL HEALTH <br /> PERMIT/SERVICES <br /> Dear Mr. Bohlke: <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets, graphs, and <br /> computer generated data for your submittal to the <br /> appropriate governmental agency. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0.05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 10, 000 Gasoline -.043 Yes <br /> Center,#2 10, 000 Gasoline - .024 Yes <br /> West 5, 000 Diesel +.014 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> William N. Savage <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />