Laserfiche WebLink
LDT 5000 Field Test Apparatus <br />Line Leak Detector Test <br />Tanknology <br />Work Order: <br />Site Name / ID: <br />Address: <br />City: <br />2324217 <br />RECEIVEL) <br />ENVIRONMEI' E 1 <br />HFV7*W nPP6ATIUr:NT <br />Date: 10/7/2015 <br />7 -ELEVEN #19976, MKT 2368 / 19976 <br />1399 N. MAIN ST. @ NORTHGATE <br />MANTECA State: CA <br />Zip: 95336 <br />Tank ID <br />T4 <br />T5 <br />Product <br />RUL <br />PUL <br />Product Line <br />1 <br />1 <br />Tested From <br />1 <br />1 <br />Existing/New <br />Existing <br />Existing <br />Mechanical/Electronic <br />Mechanical <br />Mechanical <br />Manufacturer/Model <br />Vaporless LD -200C <br />Vaporless LD -200 <br />Serial No. <br />09070785 <br />unreadable <br />Pump Operating Pressure (psi) <br />25.00 <br />24.00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />Holding PSI <br />N/A for Electronic LD's <br />25.00 <br />24.00 <br />Resiliency (ml) <br />N/A for Electronic LD's <br />120.00 <br />130.00 <br />Metering PSI <br />N/A for Electronic LD's <br />16 <br />10 <br />Opening Time (sec) <br />NIA for Electronic Lo's <br />6 <br />20 <br />Test Results <br />Pass <br />Pass <br />Technician Comments: <br />Technician Name <br />Technician Signature: <br />Jarrod Cooke <br />Environmental Compliance for Petroleum Systems <br />© 2015 Tanknology Inc., Austin, TX. All fights reserved. tanknology.com <br />Certification #: 1352 <br />Expire Date: 2/11/2017 <br />