My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO 2010 - 2014
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
M
>
MAIN
>
1399
>
2300 - Underground Storage Tank Program
>
PR0231435
>
COMPLIANCE INFO 2010 - 2014
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
8/5/2019 3:37:10 PM
Creation date
8/5/2019 11:56:00 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2010 - 2014
RECORD_ID
PR0231435
PE
2361
FACILITY_ID
FA0000916
FACILITY_NAME
7-ELEVEN INC #19976
STREET_NUMBER
1399
Direction
N
STREET_NAME
MAIN
STREET_TYPE
ST
City
MANTECA
Zip
95336
APN
21633034
CURRENT_STATUS
01
SITE_LOCATION
1399 N MAIN ST
P_LOCATION
04
P_DISTRICT
003
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
434
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sjgov.orq/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> 7-ELEVEN INC#19976 1 1399 N MAIN ST, Manteca October 13, 2014 <br /> UST System Observations <br /> 322 CCR 2636(f)(2) Line leak detector not installed ❑V ❑R ❑COS <br /> 323 CCR 2636(f)(2) Leak detector failed to detect a 3.0 gph leak at 10 psi ❑V ❑R ❑COS <br /> 324 CCR 2635(b) No spill bucket installed or failed to provide a means to keep it empty ❑V ❑R ❑COS <br /> 325 CCR 2635(b) Spill container failed to contain a minimum capacity of five gallons ■V ❑R ❑COS <br /> 326 CCR 2635(b)(2) Overfill prevention system not present,was overridden,or failed to meet overfill requirements ■V ❑R ❑COS <br /> 327 HSC 25283.5 Unburied below grade UST failed to meet exemption status ❑V ❑R ❑COS <br /> 328 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 329 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V ❑R ❑COS <br /> 330 HSC 25299(f)(2) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 331 CCR 2631.1 UST system not compatible with the substance stored ❑V ❑R ❑COS <br /> 332 HSC 25298(b) Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 333 HSC 25298(c) Failed to comply with permanent closure requirements ❑V ❑R ❑COS <br /> Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted Administration/Documentation violation ❑V ❑R ❑COS <br /> 2030 See below Unlisted Operations/Maintenance violation ❑V ❑R ❑COS <br /> 2060 See below Unlisted Design/Construction violation V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 106 CCR 2632 Monitoring and response plans not current or approved by the EHD. <br /> The monitoring plan is not current and/or not approved by the EHD. Audible and visual alarms as well as fill tube <br /> shut-off were identified in the monitoring plan uploaded to the California Environmental Reporting System (CERS), no <br /> audible and visual alarms utilized for overfill protection were noted during this inspection. The accurate monitoring plan <br /> must be uploaded to the CERS. Immediately log into CERS, make the necessary changes, and submit for review by the <br /> EHD. This is a minor violation. <br /> 319 HSC 25291(e)Water in secondary containment not removed, analyzed, and properly disposed of(pre-Jul 2003). <br /> Liquid was observed in the 87 octane STP, 87 octane fill, and 91 octane fill sumps. If water could enter into the <br /> secondary containment by precipitation or infiltration, it must be removed and disposed of properly. The service <br /> technician removed 3-gallons of liquid from 87 octane fill sump, 1/2-gallon of liquid from the 91-octane fill sump, and <br /> approximately 500-ml from the 87 octane STP sump. Ensure that all sumps and annular spaces are maintained free of <br /> liquid. This is a Class II violation. <br /> Received by(initi Inspector: hone: Date: <br /> ELENA MANZO, REHS (209) 953-7699 10/13/2014 <br /> Age 3of4 <br />
The URL can be used to link to this page
Your browser does not support the video tag.