Laserfiche WebLink
" RECEIVED <br /> = LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tankno�t�JY NOV 2 4 2014 <br /> Line Leak Detector Test g <br /> ENVIRONMENTAL HEALTH <br /> Work Order: 2319460 Date: 10/13/2014 DEPARTMENT <br /> Site Name/ID: 7-ELEVEN#19976, MKT 2368/19976 <br /> Address: 1399 N. MAIN ST.@ NORTHGATE <br /> City: MANTECA State: CA Zip: 95336 <br /> Tank ID T4 T5 <br /> Product RUL PUL <br /> Product Line 1 1 <br /> Tested From 1 1 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-200C Vaporless LD-200 <br /> Serial No. 09070785 unreadable <br /> Pump operating Pressure(psi) 25.00 24.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 25.00 24.00 <br /> N/A for Electronic LD's <br /> Resiliency(ml) 150.00 160.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 15 10 <br /> N/A for Electronic LD's <br /> Opening Time(sec) 6 23 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jarrod Cooke Certification#: 1352 <br /> Expire Date: 2/10/2015 <br /> Technician Signature: <br /> Environmental Compliance for Petroleum Systems <br /> ©2014 Tanknology Inc..Austin,TX. All rights reserved. tanknology.com <br />