Laserfiche WebLink
SA N o J Q A Q U l N Environmental Health Department <br /> -COUNTY <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Faclity Name: Facility Address: Date: <br /> STKN ARMYAVIATION SUPP FACILITY 2000 STIMSON RD STOCKTON August 08 2019 <br /> General Requirements for SPCC Plans <br /> 626 CFR 112.7(h)(1) Loading/unloading rack containment system not adequate to contain spill o V o R o COS <br /> 627 CFR 112.7(h)(2) Failed to provide vehicular departure system for loading and unloading racks o V o R o COS <br /> 628 CFR 112.7(ax1), Failure to include in the Plan discussion ofcmfamancewith Fetlerel and State requirements o V o R o COS <br /> 112.70) <br /> 628 CFR 112.7(i) Failed to evaluate field constructetl cantzberforbrittle fracture and take appropriate action o V o R o COS <br /> 630 CFR 112.7(k) Failure to provide general secondary containment or alternativefor oil-filled operational equipment .V .R .COS <br /> SPCC Plan Requirements for Onshore Facilities (excluding production facilities) <br /> 701 CFR 112.8(b)(1) Failure to ensure drainage from diked areas is restrained by valves or alternative method .V .R .COS <br /> 702 CFR 112.8(b)(2) Failed to use manual open-antldceetl design valves fix thedrainage of d iked areas .V .R .COS <br /> 703 CFR 112.8(bx3), Failed to design facility tlrainage system from undiked areas to retain in the facility .V .R .COS <br /> 112.8(bx4) <br /> 704 CFR 112.8(b)(5) Failed to provide two fa pumps for more than one continuous treatment unit .V .R .COS <br /> 705 CFR 112.8(c)(1) Containarnot compatible with oil stored antl/crstorege conditions .V .R .COS <br /> 706 CFR 112.8(c)(2) Failed to provide and maintain adequate secondary containment .V .R .COS <br /> 707 CFR 112.8(c)(3) Failure tofdfau the criteria ofthis section while allowing drainage ofuncontaminalai rainwater .V .R .COS <br /> 708 CFR 112.8(c)(3)(iv) Failed to maintain records of drainage Iran dketl areas .V .R .COS <br /> 708 CFR 112.8(c)(5) Failed to provide corrosion protection for partially burietl tanks .V .R .COS <br /> 710 CFR 112.8(c)(6) Ran failed to adequately discuss procedures to test or inspect each container for integrity a V a R .COS <br /> 711 CFR 112.8(c)(6) I Failed to pefom scheduletl tank tests or inspections by appropriately qualified personnel .V .R .COS <br /> 712 CFR 112.8(c)(6) Paled to test or inspect each container for integrity based on industry standards .V .R .COS <br /> 713 CFR 112.8(c)(7) Failed to provide eRectm leakage.1rd hon detective internal heating coils .V .R .COS <br /> 714 CFR 112.8(c)(8)(i-lie) Paled to provide each container with a high level monitoring device .V .R .COS <br /> 715 CFR 112.8(c)(8)(v) Failed to regularly test tiqub level sensing devices to ensure properoperation .V .R .COS <br /> 716 CFR 112.8(c)(9) Failed to observe effluent treatment frequently enough to dialect potential discharge .V .R .COS <br /> 717 CFR 112.8(c)(10) Failed to protmptfy torted visible discharges antl/crremoveaocemulationsofal in diked areas .V .R .COS <br /> 718 CFR 112.8(c)(11) Failed to locate prepedy or provitle ancient secondary containment for mcbile/pafable containers .V .R .COS <br /> 719 CFR 112.8(d)(1) Failed to take corrective action on burietl piping when eglosed for any reason .V .R .COS <br /> 720 CFR 112.8(dix1) Failed to provide co -cm.protection for buried piping .V .R .COS <br /> 721 CFR 112.8(dX2) Failed to capkbnk-flange connection A transfer pant and mark its origin if not F service .V .R .COS <br /> 722 CFR 112.8(dX3) Failed to design pipe supports to minimize abrasion/CarOaion and to aibwfa expansion/contraction .V .R .COS <br /> 723 CFR 112.8(dX4) Failed to regularly inspect abovegroun l valves,piping,and appurtenances .V .R .COS <br /> 724 CFR 112.8(dX4) Failed to conduct integrity and leak testing on burl piping any time it is worked on .V .R .COS <br /> 725 CFR 112.8(di)(5) Failetl to adequately warn vehicles entering faclity to protect piping and othertransfer operations .V .R .COS <br /> 728 CFR 112.8(c)(8) Ran failed to adequately describe overfill prevention methods for each container .V .R .COS <br /> Other Violations <br /> FA"3648 PRO516339 SCO01 0=812119 <br /> EHD 28-01 Rev.09127Y2018 Page 3 of 4 Aboveground Petroleum Storage Act OR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 wv✓vd.sjcehd.com <br />