Laserfiche WebLink
ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Shell Oil 5/26/04 <br /> 4315 Waterloo Rd—Stockton,CA.95205 <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer El Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: O Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Measuring tape Equipment Resolution:Example- 1/8 "increments <br /> Spill Box#87 Spill Box#91 Spill Box# Spill Box# <br /> Bucket Capacity in gallons: 15-F 5-V 15-F 5-V <br /> Bucket Depth: 10" 5" 10" 5" <br /> Wait time between filling with 15 min 15 min 15 min 15 min <br /> water and starting test: <br /> Test Start Time: 8:30 am 8:30 am 8:30 am 8:30 am <br /> Initial Reading(Rj): 7 %" 4" 8 %2" 3" <br /> Test End Time: 10:30 am 10:30 am 10:30 am 10:30 am <br /> Final Reading(RF): 7 ''/o" 4" 81/2.11 3" <br /> Test Duration: 2 hour 2 hour 2 hour 2 hour <br /> Change in Reading(RF-Rj): None None None None <br /> Pass/Fail Threshold or Criteria: ZERO LOSS ZERO LOSS <br /> Test Result: I El Pass ❑D Pass <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> All Buckets Passed <br /> Tested By: Service Station Systems, Inc. Technician: Ron W. <br /> Contractor License: 485184 <br />