xa http://zlmbra/2imbra/h/printmessage?id=99745 <br /> Zimbra cking@sjgov.org <br /> PA-1200133; Fire Prevention Review <br /> From : Kevin Jorgensen <Kevin.Jorgensen@ci.tracy.ca.us> Wed, Sep 05, 2012 06:21 PM <br /> Subject : PA-1200133; Fire Prevention Review J 1 attachment <br /> To : Corinne King <cking@co.san-joaquin.ca.us> <br /> Hi Corinne, <br /> The following comments are a result of the review of the plan submitted for Prayer Temple <br /> Christian Center New Church. <br /> 1. Is existing well to be removed from new proposed driveway in order to maintain 20' <br /> wide fire access lane? <br /> 2. There shall be NO PARKING signage as per CFC along this entire access lane (new <br /> proposed driveway). <br /> 3. Will there be any gates across access driveways to building? <br /> 4. Demonstrate appropriate turnaround capability for fire apparatus. <br /> 5. Demonstrate that 29'-9" inside radius and 47'-7" outside radius is achieved on all <br /> turning radii. <br /> 6. Sprinklers may be required for Phase I, Phase II and Phase III of this project dependent <br /> upon design per CFC. <br /> 7. Please identify two 20' x 70' structures south of the Phase I building. <br /> 8. If the building is nonsprinklered,then a class I automatic wet standpipes be required <br /> where the total occupant load is greater than 1000. <br /> 9. Provide a manual fire alarm system that activates the occupant notification system <br /> where the occupant load is greater than or equal to 300. <br /> 10. Where the occupant load is greater than 1000,the fire alarm shall initiate a signal <br /> using an emergency voice/alarm communication system. <br /> 11. Fire pumps maybe required. <br /> 12. Emergency responder radio coverage maybe required dependent upon type of <br /> construction. <br /> 13. Phase I building requires 210,000 gallon water tank unless sufficient information is <br /> provided to utilize NFPA 1142 for a smaller tank. This is based upon type V-A <br /> construction and no sprinklers. <br /> 14. Phase II building requires an additional 180,000 gallon water tank unless sufficient <br /> information is provided to utilize NFPA 1142 for a smaller tank. This is based upon type <br /> V-A construction and no sprinklers. <br /> 15. Phase III building requires an additional 180,000 gallon water tank unless sufficient <br /> information is provided to utilize NFPA 1142 for a smaller tank. This is based upon type <br /> V-A construction and no sprinklers. <br /> 16. FDC's shall be required. <br /> 2 09/06/2012 8:29 AM <br />