Laserfiche WebLink
KLEINFELDER <br /> under sunny and warm weather and in accordance with accepted guidelines using clear potable <br /> water. The approximate depth of each percolation test below existing site grade is shown on the <br /> following table. All of the holes exhibited minor sloughing or caving (about 6 inches) after <br /> presoaking. The shallow percolation test was originally approximately 3.3 feet in depth. The <br /> holes were dry prior to testing. From a fixed reference point, a marked location on the side of / <br /> PVC pipe inserted into the hole, the drop in water level is measured in approximately 30-minute 5- <br /> intervals for four hours, refilling as necessary to maintain the prescribed amount of water over <br /> the gravel (SJCEHD Procedure #2). Under the observation of a representative from the <br /> SJCEHD, the last 30-minute reading of the four-hour period is recorded and used to calculate the <br /> percolation rate in minutes per inch. The estimated percolation rates are summarized below. A <br /> copy of our field percolation test results signed by a representative from SJCEHD is attached. <br /> Details of each test can be found on the percolation test sheet. (G,/1) <br /> Test Number Depth (feet) Percolation Rate (min./inch) <br /> P-1 2.6 9 <br /> 9.5 7 <br /> 14.6 6 <br /> 7. CONCLUSIONS <br /> The results of our percolation tests indicate that suitable soil percolation strata exist at the <br /> location of the percolation tests. A suitable soil condition for septic percolation tests is defined <br /> as a stratum capable of percolating water at a rate of 60 minutes per inch (min/inch) at a depth of <br /> up to 3.5 feet below existing site grade and 30 min/inch for deeper tests. <br /> The existing permits on file with SJCEHD do not give distances from property lines for locating <br /> the system. Based on the location of the existing septic system as described to us by Mr. Gillies, <br /> we estimate that the tests were performed within approximately 10 feet of that system, as <br /> requested by Mr. Mike Huggins of SJCEHD for similar testing. We would anticipate that, with a(�,.: ) <br /> maximum of 4 full-time employees at approximately 15 gallons/day each (60 gallons/day), the <br /> estimated wastewater flow should be less than that produced by the former single-family <br /> residence (assuming 150 gallons/day). Based on the recent improvements made to the system <br /> and the estimated reduction in use, it is our opinion that the system, if functional, should be <br /> suitable for the proposed use. We would anticipate that the correct leach line lengths for the <br /> existing_E2ppLcs tem are probabl the lengths indicated on posed to the lengths <br /> given—on-the site n an. the exact len are re ire , a fine specializing in septic system <br /> inspection/repair should be co'ntacte� tic to veen�y the existing leach line lengths. <br /> 37210.601 /ST03L664 November 19,2003 <br /> 0 2003 Meinfelder,tnc. Page 4 of 7 <br />