Laserfiche WebLink
LBA Realty - Nitrate Loading Calculations <br /> Effluent Flow Rate,Q <br /> Employees GPDC Total GPD Effl. <br /> 490 7.5 3675 <br /> Uniform Waste Water Loading,W <br /> Q EffI (gpd) EffI.,cu-ft/yr Area,A(acres) Area, sq.ft. W(inches/yr) <br /> 3675 179,328 46.42 2,022,055 1.06 <br /> Deep Percolation of Rainfall <br /> Avg. Prec., in Deep Perc,% Aw(acres) R, inches per year <br /> 10.58 61% 46.42 6.45 <br /> Nw Effluent N Conc., mg/I 70' <br /> Nb Rainwater N, mg/I 1.0 <br /> d Denitrification factor 25% <br /> Nc=WNw(1-d)+RNb/W+R 8.29 mg/1-N <br /> Figure 3 -Summary of Calculations <br /> 10Page <br />