OPTION 2A <br /> ARTICLE 3, SECTION 2633/2634 <br /> MOTOR VEHTCLE FUELS ONLY <br /> CONSTRUCTION <br /> 1 . Requirements: <br /> A. Approved tank construction material <br /> B. Leak interception and detection system which complies with Article 3, <br /> Section 2631 (c) . <br /> C. Membrane liners must comply with Article 3, Section 2633(e) , (1 ) , (2) , <br /> (3) , (4) , (- 5) and are only allowed for piping systems (Department Policy) <br /> D. Demonstrate that the leak interception and detection systems protects <br /> round water from contamination (Article 3, Section 2633(f) , (1 ) , (2) , (3) , <br /> 4) , (5) , (6) , (7) . <br /> E. Pressurized piping systems must be installed with a leak detector that is <br /> capable of automatically shutting off the product pumps. <br /> 1 . Any single wall component "tank or piping" requires daily inventory <br /> reconcilliation and annual precision tests as part of the monitoring <br /> program. <br /> F. Before covering, the tank(s) and system(s) must be tested to NFPA 30, <br /> Standards. <br /> G. Before use - the tapk(s) and system(s) must be tested in accordance to <br /> NFPA 329. <br /> H. Provide soil profile'`,, f vadose zone if membrane liners are used. <br /> 10� N 2B <br /> /(leak <br /> CLE 3, SECTION 2634 <br /> R VEHICLE FUEL ONLY <br /> MONITORING <br /> 1 . Requiremenerception and detec ion system(s)). <br /> A. Floortructed on a firm ba a and sloped to a collection sump. <br /> B. Accescasings must be installed in acc3�rdance to Article 3, Section <br /> 2634 c) (1 thru 6) , (d) (1 ). \ <br /> C. Subm't written monitoring and response pla\p as stated in Article 3, <br /> Sect on 2634 (d) (1 -3) , 2634(e) (1-5). <br /> D. Hard wiring of electronic monitoring systems is required. <br /> E. Prov de manufacturer's written installation i structions. <br />