i <br /> Technical Description <br /> I <br /> Protection of the control panel and PC from electrical spikes and surges is required where history of <br /> power fluctuations occur and/or where the primary or emergency power is supplied from onsite <br /> generators. <br /> Maximum current demand is calculated at simultaneous operation of aeration,mixed-liquor transfer, <br /> and sludge return pumps. <br /> The electrical control system provides a separate alarm circuit powered by a rechargeable battery. <br /> Electrical connections and controls are installed in accordance with applicable local codes and <br /> ordinances. <br /> ' All the process pumps do not operate simultaneously in the automatic mode. In manual mode,the kw <br /> demand will vary proportionally to the cycle and the cycle duration the operator selects. - <br /> It is assumed the operator may manually operate the MLT pumps at the same time as the discharge <br /> pump, or for purposes of restabilization of the mixed liquor, the SLR pumps at the same time as the <br /> MLT pumps. The duration of manual control generally will not exceed one hour, and the electrical <br /> loads calculated for automatic operation should prove satisfactory. <br /> TREATMENT PLANT ALARM <br /> Bio-Pure systems are provided with sensors locatedinside the aeration tank and with internal main <br /> control panel circuit-breaker activation. Alarm activation capabilities are: 1) main incoming power <br /> failure to the treatment plant;2)high water level in aeration chamber;3)internal equipment overload. <br /> Alarm operation is independent of the treatment plant power source and will operate a remote light, <br /> horn, or automatic telephone dialer. <br /> t� <br /> 19 <br />