Laserfiche WebLink
Input Parameters- - - --- -- Calculation - - - ----- ---- —1 F Size Pump For--- - <br /> Orifice Size F77-:1 inches Minimum Flow Rate pet F 0.43 gpm " Design Flow Rate 56.7 gpm <br /> Residual Head at Last Orifice 5.00 feet Number of Orifices per Zone 130 Total Dynamic Hear 49.4 feet <br /> Orifice Spacing 4.0 feet Total Flow Rate per Zone F 56.7 gpm <br /> Number of Laterals per Cel 5 Number of Laterals per Zone I 5 - <br /> The nominal size of the in-line flow <br /> Lateral Length 100.0 feet %,Flow Differential 1st and Last 2.9 °h meter,if used. <br /> Lateral Pipe ClasslSchedulr 40 � <br /> — —'—`-----_._._._....----- <br /> Lateral Line Size 1.50 inches Static Heads--------. <br /> Distributing Valve Mode None Lift to Manifold r 15.0 feet <br /> Manifold Lengtt 17.0 feet Residual Head at Last Orifice 5.00 feet <br /> Manifold Pipe Class/Schedul, 40 _.._...�__.- <br /> Manifold Line Size 1.50 - inches -Frictional Head Losses ----- <br /> Lift to Manifold 15.0 feet Head Loss in Laterals 0.3 feel <br /> Calculate <br /> Transport Length 60.0 feet Head Loss through Distributing 0.0 feet <br /> Transport Pipe Class/Schedule 40 - Head Loss in Manifolc 0.6 feet <br /> Transport Line Size 2.D0 inches I Head Loss in Transport Pipe 3.0 feet <br /> Generate ChM <br /> Discharge Assembly Size 2.00 inches Head Loss through Discharge F 6.4 feet <br /> Flow Meter 2.0 inches ! Head Loss through Flow 3.0 feet <br /> Add-on'Friction Losses 15.0 feet Add-on'Friction Losses 15.0 feet <br />