Laserfiche WebLink
=TLC/CA1M Metals, OA Method 6010 <br /> EUREKA LABORATORIES, INC. Order No. : A8839 <br /> 3401 La Grande Blvd. Hazardous Waste Testing <br /> Sacramento, CA 95823 Certification No. : 108 <br /> (916) 428-1193 <br /> A.E.M. P.O. NO. : <br /> 104Z87- <br /> SAMPLE ID: BD-SS-BKGD DATE RECEIVED: 11/7/1988 <br /> ELI SAMPLE ID. : A70813-17 DATE EXTRACTED: 11/15/1988 <br /> SAMPLE LOCATION: - DATE COMPLETED: 11/17/1988 <br /> CONCENTRATION DETECTION LIMIT <br /> mMa c-(pom)1 T(Prm) 1 <br /> Silver 0 .5 0.2 <br /> Arsenic 16.8 0.6 <br /> Barium 81.6 0.05 <br /> Beryllium 0 .4 0 .2 <br /> Cadmium 0.7 0.5 <br /> Cobalt 6.9 0 .5 <br /> Chromium 19. 6 0.2 <br /> Copper 16.5 0.2 <br /> Mercury 2.9 0 .5 <br /> Molybdenum 1.6 0.5 <br /> Nickel 30.7 0. 6 <br /> Lead 11.1 1.5 <br /> Antimony 2.9 1.5 <br /> Selenium <1.5 1.5 <br /> Thallium 29. 1 0 .5 <br /> Vanadium 32.9 0.2 <br /> Zinc 39.1 0 .2 <br /> Note: <br /> Results for Arsenic, Mercury and Selenium analysis generated by Method <br /> 6010 are subject to various interference factors and instrument limitation. <br /> Therefore the results should only be interpreted as a general screen for <br /> these three elements. Analysis by the following methods which give more <br /> precise and accurate results are hichly recommended: EPA 7470/7471 for <br /> Mercury; EPA 7060/7061 for Arsenic; and EPA 7740/7741 for Selenium. <br /> * The detection limit (D/L) has been multiplied by a dilution factor of 25. <br /> � �r i Z"�� November 18, 1988 <br /> Felix Yeung Jean Hsu Dare <br /> Manager, Inorganic/Physical Chemist <br /> Testing Group <br />