SWRCB,January 2002 Page of <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Sump Manufacturer - Industry Standard X Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> s <br /> Fill Sump#1-87 Fill Sump#2-91 Fill Sump#3-Diesel Fill Sump# <br /> Sump Diameter: 42" 42" 42" <br /> Sump Depth: 42 '/2" 41" 42 '/2" <br /> Height from Tank Top to Top of 17" 19" 17" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 16" 18" 17 %2" <br /> Electrical Penetration: <br /> Condition of sump prior to Dry Dry Dry <br /> testing: <br /> Portion of Sump Tested Water Level 19" Water Level 21" Water Level 20" <br /> Sump Material: Fiberglass Fiberglass Fiberglass <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes <br /> water and starting test: <br /> Test Start Time: 7:00 7:45 8:30 <br /> Initial Reading(R,): .001 .001 .001 <br /> Test End Time: 7:30 8:15 9:00 <br /> Final Reading(RF): .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-R,): 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result: Pass Pass Pass <br /> Is there a sensor in the sump? Yes Yes Yes <br /> Does the sensor alarm when <br /> either product or water is Yes Yes Yes <br /> detected? <br /> Was sensor removed for testing? Yes Yes Yes <br /> Was sensor properly replaced and Yes Yes Yes <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> I ULnFivim <br /> MAR 14 2017 <br /> ENVIRONMENTAL <br />