Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for FOOD MART GASOLINE* as of June 14, 2017. <br /> Open violations from September 28, 2016 inspection <br /> Violation#105 - Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the EHD. The diesel tank(TA0515647) list the MLLD <br /> Manufacture as FE Petro and the MLLD Model as STP-MLD in the section Pipe Monitoring is Performed Using the <br /> Following Methods. This is not correct, the MLLD Manufacture is Vaporless and the MLLD Model is a LD2000. The <br /> monitoring plan must be uploaded to the California Environmental Reporting System (CERS). Immediately log into <br /> CERS, make the necessary changes, and submit for review by the EHD. <br /> Violation#204-Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br /> accessible on site at all times. Immediately locate and retain a copy on site. <br /> Violation #209 - Designated operator did not inspect all required items and/or the inspection reports not <br /> completed. <br /> The designated operator failed to document all the alarms from the attached alarm history on the February 2016 <br /> through March 2016 designated operator monthly inspection report and failed to check that they were responded to <br /> appropriately. The missing alarms include: <br /> -T1:87 Overfill on February 25, 2016 <br /> -T1:87 Overfill on March 10, 2016 <br /> -T1:87 Overfill on March 24, 2016 <br /> During the monthly inspection, the designated operator shall review the alarm history for the previous month, check <br /> that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br /> documentation taken in response to any alarms to the monthly report. Ensure that designated operators performing <br /> monthly inspections at this facility are including all of the required information on the reports. <br /> Page 1 of 1 <br />