Laserfiche WebLink
Jul 1719,06:47p Pro Lube Inc 209 3851235 p.15 <br /> Hazardous Waste Tank System <br /> Written Assessment per CCR Title 22 September <br /> Pro Lube, 808 S. Cherokee Lane Lodi,CA 9524D 2018 <br /> Seismic Calculation <br /> Seismic Calculation-Used Oil Tank <br /> Rectangular, Double Wail, Horizontal <br /> Materia)of Construction: steel <br /> .Length, in 117.00— <br /> Height, <br /> 17.00Hei ht in 52.00 <br /> — <br /> Working Volume, gal 928.00 <br /> S.G. of contents 0.95 <br /> Tank Wall Thickness in 0.15 <br /> ` Total Weight of Tank and Contents, lbs 8967.00 <br /> Overturning Moment Arm in 26.00 <br /> Resisting Moment Arm, in 22.50 <br /> Sds 0.59 <br /> Importance Factor 1,25 <br /> Fp, ASCE 7-10, 15.4-5 1997.40 <br /> Overturning Moment inlbf 51932.38 <br /> -Resisting Moment, inlbf 201757.50 <br /> Overturning Safety Factor- No Tension 3.89 <br /> Shear Strength of Anchor. Lbs 2320.00 <br /> _ #of Anchors 4.00 <br /> Factor of Safetv for Shear 4.65 <br /> Seismic/Anchoring findings: The tank as designed and operated and the <br /> containment area in which it is located are a40quately anchored and are <br /> seismically sound. Initials: ( ^` <br /> is <br /> Tank Integrity: The tank is a double walled tank without signs of damage or <br /> leaks. <br /> Strandberg Associztas 1r866y MS-040z; rxwivrquv e nv >eio•.,: <br /> _�cr 14 <br />