Laserfiche WebLink
s <br /> ENVIRONMENTAL . , <br /> Analytical Chemists <br /> March 28,2019 Lab ID : STK1933760 <br /> Live Oak Geo Environmental Customer : 3-16608 <br /> Quality Control - Organic <br /> Constituent Method Datc/ID Type Units Cone. QC Data DQO Note <br /> Organic <br /> 1:2-Dibromoethane(EDB) 504 03/25/19:203237BJW Blank ug/L ND <0.02 <br /> LCS ug/L 0.2482 103% 70-130 <br /> BS ug/L 0.2504 107% 70-130 <br /> BSD ug/L 0.2484 112% 70-130 <br /> BSRPD u /L 0.5806 4.1% <30 <br /> 1 3-Dibromopropane 504 03/25/19:203237BJW Blank ug/L 0.5748 111% 70-130 <br /> LCS ug/L 0.5803 96.9% 70-130 <br /> BS ug/L 0.5854 103% 70-130 <br /> BSD ug/L 0.5806 111% 70-130 <br /> BSRPD u /L 0.5806 6.3% <30 <br /> DBCP 504 03/25/19:203237BJW Blank ug/L ND <0.01 <br /> LCS ug/L 0.2481 102% 70-130 <br /> BS ug/L 0.2503 108% 70-130 <br /> BSD ug/L 0.2483 118% 70-130 <br /> BSRPD u /L 0.5806 1 8.2% S30 <br /> 13DBP 504.1 03/26/19:204241BJW CCV ug/L 7.481 102% 70-130 <br /> CCV u /L 9.975 124% 70-130 <br /> DBCP 504.1 03/26/19:204241BJW CCV ug/L 2.007 99.7% 70-130 <br /> CCV u /L 5.018 119% 70-130 <br /> DB 504.1 03/26/19:204241BJW CCV ug/L 2.008 91.1 % 70-130 <br /> CCV u /L 1 5.020 124% 70-130 <br /> Definition <br /> CCV :Continuing Calibration Verification-Analyzed to verify the instrument calibration is within criteria. <br /> Blank :Method Blank-Prepared to verify that the preparation process is not contributing contamination to the samples. <br /> LCS :Laboratory Control Standard/Sample-Prepared to verify that the preparation process is not affecting analyte recovery. <br /> BS :Blank Spikes-A blank is spiked with a known amount of analyte.It is prepared to verify that the preparation process is not <br /> affecting analyte recovery. <br /> BSD :Blank Spike Duplicate of BS/BSD pair-A blank duplicate is spiked with a known amount of analyte.It is prepared to verify that <br /> the preparation process is not affecting analyte recovery. <br /> BSRPD :BS/BSD Relative Percent Difference(RPD)-The BS relative percent difference is an indication of precision for the preparation <br /> and analysis. <br /> ND :Non-detect-Result was below the DQO listed for the analyte. <br /> O :Data Quality Objective-This is the criteria against which the quality control data is compared. <br /> Page 6 of 7 <br /> Corporate Offices&Laboratory Office&Laboratory Office&Laboratory Office&Laboratory Office&Laboratory <br /> 853 Corporation Street 2500 Stagecoach Road 563 E.Undo Avenue 3442 Empresa Drive,Suite D 9415 W.Goshen Avenue <br /> Santa Paula,CA 93060 Stockton,CA 95215 Chico,CA 95926 San Luis Obispo,CA 93401 Visalia,CA 93291 <br /> TEL:(805)392-2000 TEL:(209)942-0182 TEL:(530)343-5818 TEL:(805)783-2940 TEL:(559)734-9473 <br /> Env FAX:(805)525-4172/Ag FAX:(805)392-2063 FAX:(209)942-0423 FAX:(530)343-3807 FAX:(805)783-2912 FAX:(559)734-8435 <br /> CA ELAP Certification No.1573 CA ELAP Certification No.1563 CA ELAP Certification No.2670 CA ELAP Certification No.2775 CA ELAP Certification No.2810 <br />