Discussion of Percolation Test Results <br /> The soils within the proposed sewage disposal area of the Site have demonstrated a <br /> satisfactory percolation rate for the use of a standard septic system in accordance with <br /> the requirements of the San Joaquin County Environmental Health Department. <br /> Because of the percolation rate between 5.0 and 30.0 min/in encountered in the test <br /> hole, the San Joaquin County Environmental Health Department will require an eight- <br /> foot separation from the bottom of the dispersal system to ground water, or mitigation by <br /> system design or enhancement (see Table 2). Ground water is anticipated to be <br /> encountered approximately 103 to 104 feet below ground surface at the Site; as a <br /> result, no modification to a standard septic system should be required. <br /> Discussion of Septic System Sizing <br /> Septic system construction utilizing leach lines and seepage pits should follow the San <br /> Joaquin County On-Site Wastewater Treatment Systems Standards (2017) where <br /> applicable. <br /> LOGE 1942 Page 8 <br />