Laserfiche WebLink
MONITC .'ING SYSTEM CERTIF #*ATION <br /> CERTIFICATION / TEST DATE: October 26, 2010 <br /> Al. FACILITY A2. OWNER <br /> Name BP#29 Cruisers Manteca Name Boyett Petroleum <br /> Address 1137 W. Lathrop Road, Manteca, CA 95336 Address 601 McHenry Avenue, Modesto, CA 95350 <br /> Phone# 209-824-2760 Phone# 209-577-6000 <br /> Contact Rohda Henry Contact Rohda Henry <br /> I. RESULTS OF VACUUM/PRESSURE MONITORING EQUIPMENT TESTING <br /> Make / Model of Monitoring System: Veeder-Root TLS-350 <br /> System Type: ❑ Pressure ■ Vacuum. <br /> SensorlDME VEMEMME/z <br /> Component(s)Monitored by this Sensor: e7 product <br /> sl Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: 87 vent <br /> s2 Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: 87 annular <br /> s3 Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: e7 vapor <br /> s4 Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass, ❑ Fail <br /> Component(s)Monitored by this Sensor: 91 product <br /> s5 Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: 91 vent <br /> sg Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: diesel product <br /> s7 Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: diesel vent <br /> sg Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: diesel-91 annular <br /> slo Sensor Functionality Test Result: ■ Pass; ❑ Fail Interstitial Communication Test Results: ■ Pass; ❑ Fail <br /> Component(s)Monitored by this Sensor: <br /> Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial Communication Test Results: ❑ Pass; ❑ Fail <br /> How was interstitial communication verified? <br /> ❑ Leak Introduced at Far End of Interstitial Space:, ❑ Gauge: ❑ Visual Inspection: ■ Other(Describe in Sec.J,below) <br /> Vacuum was restored to operating levels in all interstitial spaces: ■ Yes ❑ No(If no,describe in Sec J,below) <br /> J. COMMENTS <br /> The diesel vent and annular vacuum lines were swapped,and we switched them back to the correct position. <br /> The leak was introduced at the test ports. <br /> ,If the sensor successfully detects a simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the sensor,vacuunupressure has been demonstrated to be communicating throughout the interstice. <br /> ©2010 Walton Engineering,Inc. <br /> Page 3a of 3 <br />