Laserfiche WebLink
IEU <br /> SWRCB,January 2002 Page of <br /> JUL 13 2015 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: N Tank Manufacturer ❑Industry Standard Professional Engineer <br /> .J Other(Spec) <br /> Test Method Used: ❑Pressure X Vacuum Hydrostatic <br /> 11 Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Lquipment Resolution: "x-30" Hg. <br /> Tank# 1 Tank#2 Tank# "Tank# <br /> Is Tank Exempt From Testing? No No <br /> Tank Capacity: 20K IOK <br /> Tank Material: Glass/Steel Glass/Steel <br /> Tank Manufacturer: Trusco Trusco <br /> Product Stored: Regular 87 Super 91 <br /> Wait time between applying 30 Minutes 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 9:50 9:55 <br /> Initial Reading(Rj): -10 Hg. -10 Hg. <br /> Test End Time: 11:50 10:55 <br /> Final Reading(RF): -10 Hg. -10 Hg. <br /> Test Duration: 2 Hours 1 Hour <br /> Change in Reading(RF-R,): 0 Hg. 0 Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. No loss in Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended.folloiv-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />