Laserfiche WebLink
. � �� Test Date: 12/14/2005 — <br /> YWork Order: 2239681 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Type Tank or Disp Manufacturer Model or Diam./Width/Length Depth Test Method Start Initial Level Finish Final Pass/ <br /> # Material (") 1 (") I I Time Level Change Time Result Fail <br /> STP Sump 1 REG Trusco Fiberglass 48" 61" Hydrostatic-Electronic 8:04 20" .00009 8:34 .001gph Pass <br /> STP Sump 2 SUP Trusco Fiberglass 48" 61" Hydrostatic-Electronic 8:08 20" .00007 8:38 .001gph Pass <br /> Dispenser Sump 1/2 Western Fiberglass Fiberglass 32" 28" Hydrostatic-Electronic 9:27 14" .00022 9:42 .005gph Pass <br /> Dispenser Sump 3/4 Western Fiberglass Fiberglass 32" 28" Hydrostatic-Electronic 9:25 14" .00009 9:40 .002gph Pass <br /> Dispenser Sump 5/6 Western Fiberglass Fiberglass 32" 28" Hydrostatic-Electronic 10:03 14" .00033 10:18 .007gph Pass <br /> Dispenser Sump 7/8 Western Fiberglass Fiberglass 32" 28" Hydrostatic-Electronic 10:05 14" .00001 10:0 000gph Pass <br /> Gamments <br />