PUBLIC HEALTH SERVICES PpUty <br /> SAN JOAQUIN COUNTY <br /> r• z <br /> ENVIRONMENTAL HEALTH DIVISION <br /> Ernest M. Fujimoto, M.D., M.P.H., Acting Health Officer <br /> 304 E.Weber Ave., 3rd Floor • P. O. Box 388 • Stockton, CA 95201-0388 ..F <br /> j �P <br /> 209/468-3420 °R <br /> PIPING PERFORMANCE STANDARDS (PPS 1-3) <br /> PPS-1 SINGLE WALLED SUCTION PIPING (including remote fill, gravi1y, etc.) <br /> [CA UST Regs, Section 2643(d,e)] <br /> 1. Triennial (every three years) pipeline pressure test <br /> 2. Daily suction system check <br /> PPS-2 SINGLE WALLED PRESSURIZED PIPING <br /> [CA UST Regs, Section 2643(c)] <br /> 1. Hourly monitoring capable of detecting a release of 3.0 gph and <br /> restricting or cutting off product flow, AND number 2 OR 3 below. <br /> NOTE: After 12-22-98, the leak detector shall shut off the pump should a leak <br /> occur. <br /> 2. Monthly automatic pipeline monitoring device capable of detecting a <br /> release of 0.2 gph <br /> -OR- <br /> 3. Annual pipeline pressure test <br /> PPS-3 DOUBLE WALLED PRESSURIZED PIPING <br /> [CA UST Regs, Section 2636] <br /> 1. Continuous electronic monitoring of the secondary containment <br /> 2. Hourly monitoring capable of detecting a release of 3.0 gph <br /> 3. Annual pipeline pressure test [CA Health & Safety Code, Section <br /> 25291(f) and CA UST Regs, Section 2636(g)]. <br /> NOTE: If the electronic monitoring system automatically shuts down the pump <br /> when a release is detected or the system is disconnected, number 2 and 3 above <br /> are satisfied. <br /> EH 23 012 4-24-95 <br /> A Division of San Joaquin County Health Care Services <br />