CONTAINMENT:
<br /> r �
<br /> Sump Risers_-----,
<br /> •/ Rings
<br /> - - - - - - - - - - - - - - -
<br /> - - - -
<br /> Monitor Well
<br /> f With 2" Fittings
<br /> � • H U
<br /> ' • • Annular Space
<br /> 500 1,000 6'-5 3/8" 51" 46" 4,000 3/16"
<br /> 675 1,087 4'-5 3/8" 70" 65" 5,500 3/16"
<br /> 1,000 1,404 6-5 3/8" 70" 65" 8,000 3/16"
<br /> 2,000 2,319 12'-4 5/8" 70" 65" 15,500 3/16"
<br /> 2,500 2,777 15-4 5/8" 70" 65" 19,500 3/16"
<br /> 3,000 3,233 18'-4 5/8" 70" 65" 23,000 3/16"
<br /> 3,000 3,706 8'-81/2" 102" 97" 10,700 3/16"
<br /> 4,000 4,147 24'-41/2" 70" 65" 29,500 1/4"
<br /> 4,000 4,397 11'-11/4" 102" 97" 30,500 3/16"
<br /> 5,000 5,186 13'-9 3/8" 102" 97" 38,500 1/4"
<br /> 6,000 6,171 17'-13/8" 102" 97" 48,500 1/4"
<br /> 8,000 7,745 22'-4 5/8" 102" 97" 63,500 1/4"
<br /> 10,000 8,102 15-101/2" 134 3/8" 129 3/8" 78,000 1/4"
<br /> 10,000 9,124 27'-0 5/8" 102" 97" 77,000 1/4"
<br /> 12,000 9,306 18'-11 1/2" 134 3/8" 129 3/8" 93,900 1/4"
<br /> 12,000 10,698 32'-3 7/8" 102" 97" 92,500 1/4"
<br /> 15,000 14,177 23'-7 7/8" 134 3/8" 129 3/8" 118,000 1/4"
<br /> 16,000 14,877 24'-41/2" 134 3/8" 129 3/8" 125,400 5/16"
<br /> 20,000 17,680 30'-3 3/8" 134 3/8" 129 3/8" 155,000 5/16"
<br /> 25,000 24,348 37'-71/4" 134 3/8" 129 3/8" 190,000 3/8"
<br /> 30,000 27,277 36'-4 3/4" 148 143 228,000 3/8"
<br /> 40,000 32,527 49'-0" 148 143 308,000 3/8"
<br /> Sample Specification The contractor shall provide the SuperTank®The primary tank shall be
<br /> built to UL 58 construction standards with the full thickness of steel listed in Table 3.1 of UL 58.The primary
<br /> tank shall be isolated from the external environment and secondarily contained by Fiberglass Reinforced
<br /> Plastic(200 mil nominal thickness)which is not attached to the tank except at the fittings.The primary tank
<br /> shall be factory tested to 5 psi internal pressure. Prior to shipment,the annular space shall be proof tested by
<br /> vacuum only to 20"hg vacuum.The double wall tank shall have been tested in accordance with UL 1746
<br /> and shall bear an external label indicating that the complete tank is UL listed as a jacketed secondary
<br /> containment tank. Patent #5,047,101 and #5,102,005