Laserfiche WebLink
TEST DATE : Apr 23, 1191 <br /> START TIME : 14: 49: 22 ' <br /> CLIENT : TEXACO OIL CO. <br /> LOCATION NAME : TEXACO OIL CO. <br /> LOCATION CODE : 0276 <br /> TANK CONFIGURATION : Tandem <br /> TANK CONTENTS : REG. LEAD/SUPER UNL. <br /> TANK NUMBER : 01 02 <br /> TANK DIAMETER : 91 90 in <br /> TANK CAPACITY : 10000 10000 G <br /> TANK MANUFACTURER : <br /> TANK MATERIAL : Fibreglass Fibreglass <br /> TANK REGISTRATION # : <br /> TANK DATE INSTALLED <br /> INITIAL DIPPED FUEL LEVEL : 77. 00 84. 00 in <br /> INITIAL DIPPED WATER LEVEL : 0. 00 0. 00 in <br /> POST PUMPING WATER LEVEL : 0. 00 0. 00 in <br /> -T-its al f< -I-Er ESI- F?EE E&LJ L. <br /> TEST INITIAL WATER LEVEL : 0.00 0. 00 in <br /> TEST FINAL WATER LEVEL : 0.00 0.00 in <br /> WATER INGRESS : 0. 00 0. 00 in <br /> BUBBLE SIGNATURES : No No <br /> VACU-TECT TEST RESULT : Passed Passed <br /> COMMENTS: TESTED TANKS 1 (RL)AND 2(SUL) . <br /> CONCLUSION: TANK 1 SYSTEM FAILED. TANK 2 TESTED TIGHT. <br /> L_ I [NJ 1= -I"-E=7 1=3-r- FA-1LE 10 -1- <br /> TEST RATE TEST RATE <br /> LINE RESULT PRESSURE OF LOSS RESULT PRESSURE� <br /> #1 Passed 50 PSI 0. 00 GPH Passed 50 PSI 0. 00 GPH <br /> #2 <br /> #3 <br /> #4 <br /> #5 <br /> #6 <br /> COMMENTS: TESTED LINES 1-A AND 2-A. <br /> CONCLUSION: LINE 1-A . LINE 2-A . <br /> This test was conducted in accordance with U.S. EPA Rule 40 CFR Pats 20 and 281. <br /> -----� <br /> RANNI 8DUlLY VACU-TECT(tm) Test Number <br /> TANKNOLOGY - UNDERGROUND LEAK DETECTION SYS7EM (V3. 10) Page 13 <br /> TEXACO OIL CO. HOU9104-lT8I2317'26314-03 - Apr 23, 1991, 15:52 <br />