Laserfiche WebLink
AUG-21-2004 17 22 SERUICE STATION SYSTEM 408 971 0135 P.06 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Shell Oil Date: 7/26/04 <br /> 6131 Pacific Ave—Stockton,CA.95207 <br /> Test Method Developed By: ❑Spill Bucket Manufacturer Z Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ® Hydrostatic ^ <br /> 0 Other(Speer) <br /> Equipment Resolution: <br /> Test Equipment Used Measuring tape <br /> Example- 1/8"increments <br /> MMMMISpill Box#87 Spill Bose#89 Spil!Box#9I Spill Box# <br /> Bucket Capacity in gallons: 5-V 15-F 5-V 15-F 5-V 15-F j <br /> Bucket Depth: 11" 17" 111, 17" )III 17" <br /> Wait time between filling with 20 ruin 20 min 20 min 20 min 20 min 20 min <br /> water and starting test: <br /> Test Start Time: 8:50 am 8:51 am 8:52 am 8:53 am 8:54 am 8:55 am <br /> Initial Reading(RI): 5" 3 Y/" 5 %2" 4" 4" 3" <br /> Test End Time: 9:50 am 9:51 am 9:52 am 9:53 am 9:54 am 9:55 am <br /> Final Reading(Rr): S" 3 5 'h" 4" 4" 3" <br /> Test Duration: 1 hour I hour 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(Rp-Ro): None None None L None None None <br /> Pass/Fail Threshold or Criteria: ZERO DOSS ZERO LOSS tZERO LOSS <br /> 1? I <br /> k ,.o`1 ar YG Aaa 'UNa{�6�'t 't�M�� }' •:i,��. <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> All Buckets Passed <br /> Tested By: Service Station Systems, Inc. Technician: Ron W. <br /> Contractor License: 485184 <br /> TOTAL P.06 <br />