Laserfiche WebLink
PLAN CHECK REVIEW FOR 6131 PACIFIC AVENUE <br /> REMOVAL PLAN DEFICIENCIES: <br /> (� 1) NEED TO COMPLETE AND SUBMIT THE "APPLICATION FOR PERMIT FOR <br /> UNDERGROUND STORAGE TANK CLOSURE" <br /> 2) NEED TO SUBMIT MONITORING AND RESPONSE PLAN FOR SAN JOAQUIN <br /> COUNTY NOT STANISLAUS COUNTY (AGAIN) <br /> 3) PERMIT REQUIRED FROM FIRE DEPT. TO CUT UP UGST. <br /> OTHERWISE EVERYTHING ELSE ON REMOVAL PLAN LOOKS GOOD. <br /> NOW. . . . <br /> INSTALLATION PLAN DEFICIENCIES (OR QUESTIONS) : <br /> "1) NEED DETAILED SITE MAP SHOWING LOCATION OF UTILITIES (WATER, <br /> SEWER AND ELECTRICAL LINES) . <br /> �\ 2) THE MONITORING AND RESPONSE PLAN IS GREAT, HOWEVER, IT NEEDS TO <br /> INCLUDE A DESCRIPTION OF PROPOSED METHODS AND EQUIPMENT TO BE USED <br /> FOR REMOVING THE HAZARDOUS SUBSTANCES, INCLUDING THE LOCATION AND <br /> AVAILABILITY OF REQUIRED EQUIPMENT. <br /> (,-3) ALSO, ACCORDING TO THE H&S CODE, IF THE UGST IS DESIGNED TO <br /> MAINTAIN A WATER LEVEL IN THE SECONDARY CONTAINMENT, THE TANK SHALL <br /> BE EQUIPPED WITH A SAFE METHOD OF REMOVING ANY EXCESS WATER TO A <br /> HOLDING FACILITY AND THE OWNER OR OPERATOR SHALL INSPECT THE <br /> HOLDING FACILITY MONTHLY FOR THE PRESENCE OF EXCESS WATER OVERFLOW. <br /> IF EXCESS WATER IS PRESENT IN THE HOLDING FACILITY, THE PERMIT <br /> HOLDER SHALL PROVIDE A MEANS TO ANALYZE THE WATER FOR HAZARDOUS <br /> SUBSTANCE CONTAMINATION AND A MEANS TO DISPOSE OF THE WATER, IF SO <br /> CONTAMINATED, AT AN AUTHORIZED DISPOSAL FACILITY. SOMEHOW, THIS <br /> NEEDS TO BE ADDRESSED IN THE MONITORING AND RESPONSE PLAN. <br /> -i4) OH YEAH, ONE OTHER THING IN THE MONITORING AND RESPONSE PLAN. <br /> UNDER ELECTRONIC MONITORING YOU MENTIONED IN THE EVENT OF A LEAK <br /> THE PRODUCT WILL BE CONTAINED IN THE ANNULAR SPACE, BUT ISN'T THE <br /> ANNULAR SPACE FILLED WITH WATER? <br />