Laserfiche WebLink
2 r ^e <br /> 2 <br /> September 11 , 1956 <br /> 1932kton NorthnEl1ed Pinalhool District FR'�,� SF /y <br /> C Stockton , California 95205 <br /> { F <br /> N Attn: Bill Harmening <br /> C <br /> E Re : Petro-Tite Tank Test <br /> N F Dear Bill : <br /> T <br /> A On September 6 , 1986 , we performed a Petro-Tite Tank Test <br /> L o at 1932 No . E1 Pinal , Stockton , California. The test was <br /> performed by Thomas Franken , E .P . E . Technician . The NFPA code <br /> B 329 .02 criteria for a tight tank test is a tolerance of +- .050 <br /> !' gallons per hour . Because of the almost infinite variables <br /> involved , this is not intended to be a mathematical tolerance <br /> E 2 and is not the permission of actual leakage . <br /> T <br /> 7 PRECISION TEST <br /> 6 <br /> Tank 1 - East <br /> 6 <br /> y Size - 500 gallon tank <br /> L T Product - Solvent <br /> U 0 The test showed a negative . 113 gallons per <br /> C hour . Based on the above criteria , we find <br /> K the tank tested, mathematically failed . We <br /> T recommend isolating the tank and retesting . <br /> 0 <br /> N <br /> This concludes our test and findings on September 6 , 1986 . <br /> C If you have any questions regarding the results , please con- <br /> A tact me . An extra copy has been included for you to notify <br /> 9 your local County Health Department , Environmental Health . If <br /> 5 you have any questions on what your next step should be , <br /> E 2 please contact your local Health Department immediately . <br /> 0 <br /> E Sincerely/InIken 2 <br /> 9 Aeas Fr <br /> 9 <br /> 9 Certified Tank Testing Technician <br /> 4 <br /> 3 <br /> N TF/bm <br /> C 2 Encl . <br /> 2 <br />