Laserfiche WebLink
2 <br /> 5 <br /> , E 2 <br /> 5 August 6 , 1986 <br /> P Stockton Unified School District <br /> ' � A <br /> C 701 North Madison <br /> I Stockton , California 95203 <br /> © F <br /> N 1 Attn : Bill Harmening <br /> E A Re: Petro-Tite Tank Test <br /> N V <br /> .r E Dear Bill : <br /> P On July 31 , 1986 , we performed a Petro-Tite Tank Test at <br /> L o the Corporation Yard , 1932 No . E1 Pinal , Stockton , California . <br /> The test was performed by Thomas Franken , E .P . E . Technician . <br /> B The NFPA code 329 .02 criteria for a tight tank system is a <br /> O tolerance of +- . 050 gallons per hour . Because of the almost <br /> P X infinite variables involved this is not intended to be a <br /> E 2 mathematical tolerance and is not the permission of actual <br /> T o leakage . <br /> R 7 <br /> (� 6 PRECISION TEST <br /> L <br /> E S Tank 3 - South <br /> V TO Size - 10 ,000 gallon tank <br /> Product - Diesel <br /> M K The test showed a positive .032 gallons per <br /> T hour . Based on the above criteria , we find <br /> O the tank tested mathematically tight . <br /> E " <br /> N This concludes our test and findings on July 31 , 1986 . If <br /> G A you have any questions regarding the results , please contact <br /> t your local County Health Department , Environmental Health . If <br /> 9 you have any questions on what your next step should be , please <br /> N 5 contact your local Health Department immediately . <br /> E 2 <br /> E Sincerely , <br /> 2 /vn <br /> N 0 Thomas Franken <br /> G9 <br /> `./ Certified Tank Testing Technician <br /> 9 <br /> 3 <br /> N TF/bm <br /> p E n c 1 . <br /> h <br /> z <br /> /SERV/CFS4 <br />