Laserfiche WebLink
ITTSIntegrity Task Testing Systems, Inc. <br /> January 26 , 1991 <br /> Mr. Charles Leubner <br /> Stockton Unified School District <br /> 1932 North E1 Pinal <br /> Stockton, California 95205 <br /> Dear Mr. Leubner: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets, graphs, and <br /> computer generated data for your submittal to the <br /> appropriate governmental agency. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> #1 10 , 000 Diesel -.004 Yes <br /> #3 10, 000 Diesel -.004 Yes <br /> #2 12 , 000 Diesel -.012 Yes <br /> Southeast 8, 000 U/L Gas +.015 Yes <br /> Northwest 12 , 000 Reg Gas -.015 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sinc rely, <br /> W. N. Savage <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209)466-8036 <br />