Laserfiche WebLink
INI r-GRITY TANK TESTING SER*ES <br /> DIVISION OF OIL EQUIPMENT SERVICE <br /> P. O. BOX 950, SAN ANDREAS, CA. 95249 <br /> January 29, 1994 <br /> Stockton Unified School District Site: 1932 N. EI Pinal <br /> Attention: Charles Leubner <br /> 1944 N. EI Pinal <br /> Stockton, Ca. <br /> Dear Mr. Leubner, <br /> Following is a summary of the precision testing we recently conducted on your <br /> underground storage at the above site: <br /> Enclosed are copies of the test worksheet, graphs, and/or computer generated <br /> summations for your submittal to the appropriate governmental agency. <br /> A tank system may be considered tight, according to the current regulations if the test <br /> results shown below do not exceed 0.05 GPH. If the results are beyond this parameter <br /> an unauthorized release may have occurred, and you should consider taking remedial <br /> action. <br /> Tank#/Location Product Contained Loss/Gain GPH Tank Tight <br /> N/W #1 Diesel Fuel +.005 Yes <br /> N/E #3 Diesel Fuel -.023 Yes <br /> S/E #2 Diesel Fuel -.024 Yes <br /> S/E #8 Gasoline +.002 Yes <br /> N/W Gasoline -.001 Yes <br /> Please advise if you needed additional assistance or information. <br /> Sincerely, <br /> QZU s <br /> W. N. Savage <br /> Certified Tester <br /> SAN ANDREAS 7541808 STOCKTON 474-1375 TOLL FREE 800 262-8378 <br />